1.0 |
Load Type |
AC Motor |
2.0 |
Rating |
|
2.1 |
Horsepower |
3 |
2.2 |
Motor (kW) |
2.2 |
2.3 |
Capacity (kVA) |
4.5 |
2.4 |
Output Current (Amps) |
11 |
3.0 |
Rated Input |
|
3.1 |
Input Voltage |
200 - 240VAC ±10% |
3.2 |
Phase |
1 |
3.3 |
Frequency |
50/60 ±5% |
4.0 |
Rated Output |
|
4.1 |
Voltage |
200 - 240VAC ±10% |
4.2 |
Phase |
3 |
4.3 |
Frequency |
0.5 - 400 Hz |
5.0 |
Control Method |
Sine-Wave (PWM) control |
6.0 |
Frequency Range |
0.5 - 400 Hz |
7.0 |
Frequency Accuracy |
|
7.1 |
Digital Command |
± 0.01% of the max. frequency |
7.2 |
Analog Command |
± 0.2% of the max. frequency |
8.0 |
Frequency Setting Resolution |
|
8.1 |
Digital |
0.1 Hz |
8.2 |
Analog |
Max. Freq./100 |
9.0 |
Volt./Freq. Characteristics |
Setting available for constant torque, reduced torque, sensorless vector |
10.0 |
Overload Current Rating |
150%, 60 seconds |
11.0 |
Acceleration/Deceleration Time |
0.1 ~ 3000 sec. (linear/curve, accel./decel.) Second stage accel./decel. setting available |
12.0 |
Braking |
|
12.1 |
Dynamic Braking |
Approx. 100% |
12.2 |
DC Braking |
Operating frequency, time and braking force variable |
13.0 |
Input Signal |
|
13.1 |
Frequency Setting |
|
13.1.1 |
Digital Operator Panel |
Up(1) and Down(2) keys/value setting keys |
13.1.2 |
Potentiometer |
Analog Setting |
13.1.3 |
External Signal |
0 ~ 10 VDC (input impedence 10k ohms), 4 ~ 20 mA (input impedence 250k ohms) Potentiometer: 1k to 2k ohms, variable resistor. The frequency command is the maximum frequency at 9.8V for input voltage 0 - 10 VDC, or at 19.6 mA for input current 4 ~ 20 mA. If this characteristic is not convenient contact Drives Warehouse. |
13.2 |
Forward/Reverse/Start/Stop |
|
13.2.1 |
Digital Operator Panel |
Run/Stop (Forward/Reverse run change by command) |
13.2.2 |
External Signal |
Forward RUN/STOP (1a contact) |
13.3 |
Intelligent Input Terminals |
FW (Forward run command), RV (reverse run command, CF1~CF4 (multi-stage speed setting), JG (jogging command), 2CH (2-stage acceleration/deceleration command), FRS (free run stop command), EXT (external trip), USP (USP function), SFT (soft lock), AT (analog current input select signal), RS (reset), PTC (thermal protection). |
14.0 |
Output Signal |
|
14.1 |
Intelligent Output Terminal |
RUN (running signal), FA1,2 (frequency arrival signal), OL (overload advance notice signal), OD (deviation signal at PID control), AL (alarm signal) |
14.2 |
Frequency Monitor |
PWM output: Select analog output frequency monitor, analog output current monitor or digital output frequency monitor |
15.0 |
Other Functions |
AVR function, upper/lower limiter, PID control, carrier frequency change, frequency jump, electronic thermal level adjustment, gain/bias setting function, retry function |
16.0 |
Protective Function |
Overcurrent, overvoltage, undervoltage, overload, extreme high/low temperature, CPU error, memory error, ground fault detection at startup, internal communication error. |
17.0 |
Environmental Conditions |
|
17.1 |
Operating Temp. |
-10 ~ 50ºC |
17.2 |
Storage Temp. |
-10 ~ 70ºC |
17.3 |
Humidity |
20 ~ 90 % RH (no condensation) |
17.4 |
Vibration |
5.9 m/s² (0.6G), 10 ~ 55 Hz |
17.5 |
Location |
Less than 1000 m of altitude or less, indoors (no corrosive gases or dust) |
18.0 |
Mechanical Properties |
|
18.1 |
Color |
Black |
18.2 |
Height |
5.04 inches (128mm) |
18.3 |
Width |
4.25 inches (108mm) |
18.4 |
Depth |
6.71 inches (170.5mm) |
18.5 |
Weight (lbs) |
4.0 |
19.0 |
Options |
Remote operator Dynamic braking resistor AC reactor DC reactor Noise filter |