ITEM #25 E-T-A Circuit Protection and Control ESX10-100-DC24V-2A-E Electronic Circuit Protector ESX10 Issue C 5 - 27 5 Description Technical data (Tambient = 25 °C, operating voltage US = DC 24 V) ESX10 Electronic circuit protector type ESX10 is designed to ensure selective disconnection of DC 24 V load systems. DC 24 V power supplies, which are widely used in industry today, will shut down the output in the event of an overload with the result that one faulty load in the system can lead to complete disconnection of all loads. As well as an unidentified failure this also means stoppage of the whole system. Through selective disconnection the ESX10 responds much faster to overload or short circuit conditions than the switch-mode power supply. This is achieved by active current limitation. The ESX10 limits the highest possible current to values between 1.3 to 1.8 times the selected rated current of the circuit protector. Thus it is possible to switch on capacitive loads of up to 20,000 μF lamp loads, but they are disconnected only in the event of an overload or short circuit. For optimal alignment with the characteristics of the application the current rating of the ESX10 can be selected in fixed values from 0.5 A...12 A. Failure and status indication are provided by a multicolour LED and an integral short-circuit-proof status output or a potential-free signal contact. The ESX10, with a width of only 12.5 mm, can be plugged into the E-T-A power distribution socket Module 17plus ensuring ease of installation and saving space in control cabinets. Upon detection of overload or short circuit in the load circuit, the MOSFET of the load output will be blocked to interrupt the current flow. The MOSFET and the load circuit may be re-activated via the remote electronic reset input or manually by means of the ON/OFF button. When starting up the system, the load circuit may also be manually disconnected. Features Approvals � Selective load protection, electronic trip characteristics. � Active current limitation for safe connection of capacitive loads up to 20,000 μF and on overload/short circuit. � Current ratings 0.5 A...12 A. � Reliable overload disconnection with 1.1 x IN plus, even with long load lines or small cable cross sections (see table 3). � Manual ON/OFF button (S1). � Control input IN+ for remote ON/OFF signal (option). � Clear status and failure indication through LED, status output SF or Si contact F. � Electronic reset input RE (option). � Integral fail-safe element. � Width per unit only 12.5 mm. � Plug-in mounting utilising power distribution system Module 17plus or SVSxx optionally (see product group Power distribution systems) Authority Voltage rating Current ratings UL 2367 DC 24 V 0.5...12 A UL 508 DC 24 V 0.5...12 A CSA C22.2 No: 14 DC 24 V 0.5...12 A Attention: � The user should ensure that the cable cross sections of the relevant load circuit are suitable for the current rating of the ESX10 used. � Automatic start-up of machinery after shut down must be prevented (Machinery Directive 98/37/EG and EN 60204-1). In the event of a short circuit or overload the load circuit will be disconnected electronically by the ESX10. Operating data Operating voltage US DC 24 V (18...32 V) Current rating IN fixed current ratings: 0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A, 12 A Closed current I0 ON condition: typically 20...30 mA depending on signal output Status indication � multicolour LED: by means of GREEN: unit is ON, power-MOSFET is switched on - status output SF ON, supplies + DC 24 V ORANGE: in the event of overload or short circuit until electronic disconnection RED: - unit electronically disconnected - load circuit/Power-MOSFET OFF OFF: - manually switched off (S1 = OFF) or device is dead - undervoltage (US < 8 V) - after switch-on till the end of the delay period � status output SF (option) � potential-free signal contact F (option) � ON/OFF/ condition of switch S1 Load circuit Load output Power-MOSFET switching output (high side switch) Overload disconnection typically 1.1 x IN (1.05...1.35 x IN) Short-circuit current IK active current limitation (see table 1) Trip time see time/current characteristics for electronic disconnection typically 3 s at ILoad > 1.1 x IN typically 3 s...100 ms at ILoad > 1.8 x IN (or 1.5 x IN/1.3 x IN) Temperature disconnection internal temperature monitoring with electronic disconnection Low voltage monitoring load output with hysteresis, no reset necessary load “OFF� at US < 8 V Starting delay tstart typically 0.5 sec after every switch-on and after applying US Disconnection of load circuit electronic disconnection Free-wheeling circuit external free-wheeling diode recommended with inductive load Several load outputs must not be connected in parallel www.e-t-a.com Electronic Circuit Protector ESX10 5 - 28 Issue C 5 Status output SF ESX10-104/-106/-124/-127 Electrical data plus-switching signal output, connects US to terminal 12 of module 17plus nominal data: DC 24 V / max. 0.2 A (short circuit proof) status output is internally connected to GND with a 10 kOhm resistor Status OUT ESX10-104/-106/ -124 (signal status OUT), at US = +24 V +24 V = S1 is ON, load output connected through 0V = S1 is ON, load output blocked and/or switch S1 is OFF Status OUT ESX10-127 (signal status OUT inverted), at US = +24 V +24 V = S1 is ON, load output blocked, red LED lighted 0 V = S1 is ON, load output connected through and/or switch S1 is in OFF position OFF condition 0 V level at status output when: � switch S1 is in ON position, but device is still in switch-on delay � switch S1 is OFF, or control signal OFF, device is switched off � no operating voltage US Signal output F ESX10-101/-102/-103/-105/-106/-115/-125 Electrical data potential-free signal contact max. DC 30 V/0.5 A, min. 10 V/10 mA ON condition LED green voltage US applied, switch S1 is in ON position no overload, no short circuit OFF condition LED off � device switched off (switch S1 is in OFF position) � no voltage US applied Fault condition LED orange overload condition > 1.1 x IN up to electronic disconnection Fault condition LED red electronic disconnection upon overload or short circuit device switched off with control signal (switch S1 is in ON position) ESX10-101 single signal, make contact contact SC/SO-SI open ESX10-102 single signal, break contact contact SC/SO-SI closed ESX10-103 group signal change-over contact contact SC-SO open, SC-SI closed ESX10-105/-106/-115/-125 group signal, make contact contact SC-SO open Fault signal output fault conditions: � no operating voltage US � ON/OFF switch S1 is in OFF position � red LED lighted (electronic disconnection) Technical data (Tambient = 25°C, operating voltage US = DC 24 V) Technical data (Tambient = 25°C, operating voltage US = DC 24 V) Reset input RE ESX10-124/-125/-127 Electrical data voltage: max. + DC 32 V high > DC 8 V ≤ DC 32 V low ≤ DC 3 V > 0 V power consumption typically 2.6 mA (+DC 24 V) min. pulse duration typically 10 ms Reset signal RE The electronically blocked ESX10-124/-127 (= terminal 13,14 or 12 may remotely be reset via an external of Module 17plus) momentary switch due to the falling edge of a +24 V pulse. Caution: unused slots The reset signal will be fed in terminal 13, 14 have to be fitted with or 12 of Module 17plus and is internally jumpers pre-wired. The reset simultaneously affects all blocked ESX10-124/-127 channels of the power distribution system, all switched on ESX10-124/-127 channels remain unaffected. With type ESX10-125 the reset only affects the device concerned. By connecting the individual terminals 12 of the Module 17plus a joint reset signal for all ESX10-125 may be generated. Control input IN+ ESX10-115 Electrical data see reset input RE Control signal IN+ +24 V level (HIGH): device will be switched on by a remote ON/OFF signal 0 V level (LOW): device will be switched off by a remote ON/OFF signal Switch S1 ON/OFF unit can only be switched on with S1 if a HIGH level is applied to IN+ General data Fail-safe element: backup fuse for ESX10 not required because of the integral redundant fail-safe element Blade terminals 6.3 mm to DIN 46244-A6.3-0.8 Housing moulded Mounting plug-in mounting utilising power distribution system Module 17plus or SVSxx Ambient temperature 0...+50 °C (without condensation, see EN 60204-1) Storage temperature -20...+70 °C Humidity 96 hrs/95 % RH/40 °C to IEC 60068-2-78, test Cab. climate class 3K3 to EN 60721 Vibration 3 g, test to IEC 60068-2-6 test Fc Degree of protection housing: IP30 DIN 40050 terminals: IP00 DIN 40050 EMC emission: EN 61000-6-3 (EMC directive, CE logo) susceptibility: EN 61000-6-2 Insulation co-ordination 0.5 kV/2 pollution degree 2 (IEC 60934) re-inforced insulation in operating area dielectric strength max. DC 32 V (load circuit) Insulation resistance (OFF condition) n/a, only electronic disconnection Approvals UL 2367, File # E306740 Solid State Overcurrent Protectors UL 508, File # E322549 CSA C22.2 No: 14, File 16186 CE logo Dimensions (W x H x D) 12.5 x 70 x 60 mm Mass approx. 40 g Table 1: voltage drop, current limitation, max. load current current rating typically voltage drop active current max. load current at 100 % ON duty IN UON at IN limitation (typically) TU = 40 °C TU = 50 °C 0.5 A 70 mV 1.8 x IN 0.5 A 0.5 A 1 A 80 mV 1.8 x IN 1 A 1 A 2 A 130 mV 1.8 x IN 2 A 2 A 3 A 80 mV 1.8 x IN 3 A 3 A 4 A 100 mV 1.8 x IN 4 A 4 A 6 A 130 mV 1.8 x IN 6 A 5 A 8 A 120 mV 1.5 x IN 8 A 7 A 10 A 150 mV 1.5 x IN 10 A 9 A 12 A 180 mV 1.3 x IN 12 A 10.8 A Attention: when mounted side-by-side without convection the ESX10-0.. should not carry more than 80 % of its rated load with 100 % ON duty due to thermal effects. Electronic Circuit Protector ESX10 Issue C 5 - 29 5 B(190110) Ordering information Type No. ESX10 Electronic Circuit Protector for DC 24 V applications Version 1 standard, without physical isolation in the event of a failure Signal input 0 without signal input 1 with control input IN+, only ESX10-115 2 with reset input RE, only ESX10-124, ESX10-125, ESX10-127 Signal outputs 0 without, only ESX10-100 1 signal output F (single signal, N/O), only ESX10-101 2 signal output F (single signal, N/C), only ESX10-102 3 signal output F (group signal, change-over), only ESX10-103 4 status output SF (+24 V = OK), only ESX10-104, ESX10-124 5 signal output F (group signal, N/O), ESX10-105, ESX10-115, ESX10-125 6 signal output F (group signal, N/O), status output SF +24 V = OK, only ESX10-106 7 status output inverted, 0 V = OK, only ESX10-127 Operating voltage DC 24 V rated voltage DC 24 V Current rating 0.5 A 1 A 2 A 3 A 4 A 6 A 8 A 10 A 12 A ESX10 - 1 0 5 - DC 24 V - 6 A ordering example Terminal wiring diagram ESX10-124 ESX10-124-… Rsense Failsafe LINE (+) DC 24 V LOAD (+) load output GND (-) SF status output RE reset input RE reset input status indication green/orange/red S1 ON/OFF electronic control unit Schematic diagram ESX10-124 ESX10 Elektronischer Sicherungsautomat Electronic Circuit Protector ESX10-1xx-DC 24 V-xxA Germany 1 11 2 13 14 12 LINE + GND LOAD + RE RE SF Status OUT Reset IN Failsafe UL 2367 cUL 508 Please note: � The user should ensure that the cable cross sections of the relvant load circuit are suitable for the current rating of the ESX10 used. � Automatic start-up of machinery after shut down must be prevented (Machinery Directive 98/37/EG and EN 60204-1). In the event of a short circuit or overload the load circuit will be disconnected electronically by the ESX10. Description of ESX10 signal inputs and outputs (wiring diagrams) see next page. Table 2: ESX10 - product version version signal input signal output signal output F status output SF ESX10 -... control input ON/OFF +24 V Control IN+ reset input +24 V RE single signal N/O single signal N/C group signal N/O group signal change-over status OUT +24 V = OK status OUT 0 V = OK -100 -101 x -102 x -103 x -104 x -105 x -106 x x -115 x x -124 x x -125 x x -127 x x Electronic Circuit Protector ESX10 5 - 30 Issue C 5 ESX10 Signal inputs / outputs (wiring diagram) Failsafe 1 LINE + 11 GND 2 LOAD + 13 RE 14 RE 12 SF Status OUT Reset IN ESX10-124-... with reset input RE (+DC 24 V↓) with status output SF (+24V = load output ON) Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO 12 SI Signal ESX10-101 without signal input with signal output F (single signal, N/O) operating condition: SC/SO-SI closed fault condition: SC/SO-SI open Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO 12 SI Signal ESX10-102 without signal input with signal output F (single signal, N/C) operating condition: SC/SO-SI open fault condition: SC/SO-SI closed Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO 12 SI Signal ESX10-103 without signal input with signal output F (group signal, change-over) operating condition: SC/SO closed, SC-SI open fault condition: SC/SO open, SC-SI closed Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO ESX10-104 without signal input with status output SF (+24 V = load output ON) 12 SF Status OUT Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO Signal ESX10-105 without signal input with signal output F (group signal, N/O) operating condition: SC-SO closed fault condition: SC-SO open Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO Signal 12 SF Status OUT ESX10-106 without signal input with signal output F (group signal, N/O) with status output SF (+24 V = load output ON) operating condition: SC-SO closed fault condition: SC-SO open Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO Signal 12 IN + Control IN ESX10-115-... with control input IN+ (+DC 24 V) with signal output F (group signal, N/O) operating condition: SC-SO closed fault condition: SC-SO open Failsafe 1 LINE + 11 GND 2 LOAD + 13 SC 14 SO Signal 12 RE Reset IN ESX10-125-... with reset input RE ( +DC 24 V ↓) with signal output F (group signal, N/O) operating condition: SC-SO closed fault condition: SC-SO open ESX10 signal inputs / outputs (wiring diagrams) Signal contacts are shown in the OFF or fault condition. Failsafe 1 LINE + 11 GND 2 LOAD + 13 RE 14 RE 12 SF Status OUT Reset IN ESX10-127-... with reset input RE (+DC 24 V ↓) with status output SF inverted, 0V = load output ON operating condition: SF 0V = OK fault condition: SF +24 V Failsafe 1 LINE + 11 GND 2 LOAD + ESX10-100 without signal input/output 13 14 operating condition: SF +24 V = OK fault condition: SF 0V operating condition: SF +24V = OK fault condition: SF 0V Electronic Circuit Protector ESX10 Issue C 5 - 31 5 disconnection typically 1.1 x IN current limitation typically 1.8 x IN *1) IK 10000 1000 1 2 4 trip time in seconds ...times rated current 100 10 1 0.1 0.01 0 3 5 1.8 x IN *1) 5 Time/Current characteristic curve (TA = 25 °C) Table 3: Reliable trip of ESX10 *1) current limitation typically 1.8 x IN times rated current at IN = 0.5 A...6 A current limitation typically 1.5 x IN times rated current at IN = 8 A or 10 A current limitation typically 1.3 x IN times rated current at IN = 12 A � The trip time is typically 3 s in the range between 1.1 and 1.8 x IN *1). � Electronic current limitation occurs at typically 1.8 x IN *1) which means that under all overload conditions (independent of the power supply and the resistance of the load circuit) the max. overload before disconnection will not exceed 1.8 x IN *1) times the current rating. Trip time is between 100 ms (short circuit current IK) and 3 sec (at overload with high line attenuation). � Without this current limitation a considerably higher overload current would flow in the event of an overload or short circuit. Reliable trip of ESX10 with different cable lengths and cross sections Resistivity of copper �0 = 0.0178 (Ohm x mm2) / m US = DC 19.2 V (= 80 % v. 24 V) voltage drop of ESX10 and tolerance of trip point (typically 1.1 x IN = 1.05 ... 1.35 x IN) have been taken into account. ESX10-selected rating IN (in A) 3 6 e. g. trip current Iab = 1.25 x IN (in A) 3.75 7.5 ESX10 trips after 3 s Rmax in Ohm = (US / Iab) - 0.050 5.07 2.51 The ESX10 reliably trips from 0 Ohm to max. circuitry resistance Rmax Cable cross section A in mm2 0.14 0.25 0.34 0.5 0.75 1 1.5 cable length L in meter cable resistance in Ohm = (R0 x 2 x L) / A (= single length) 5 1.27 0.71 0.52 0.36 0.24 0.18 0.12 10 2.54 1.42 1.05 0.71 0.47 0.36 0.24 15 3.81 2.14 1.57 1.07 0.71 0.53 0.36 20 5.09 2.85 2.09 1.42 0.95 0.71 0.47 25 6.36 3.56 2.62 1.78 1.19 0.89 0.59 30 7.63 4.27 3.14 2.14 1.42 1.07 0.71 35 8.90 4.98 3.66 2.49 1.66 1.25 0.83 40 10.17 5.70 4.19 2.85 1.90 1.42 0.95 45 11.44 6.41 4.71 3.20 2.14 1.60 1.07 50 12.71 7.12 5.24 3.56 2.37 1.78 1.19 75 19.07 10.68 7.85 5.34 3.56 2.67 1.78 100 25.34 14.24 10.47 7.12 4.75 3.56 2.37 125 31.79 17.80 13.09 8.90 5.93 4.45 2.97 150 38.14 21.36 15.71 10.68 7.12 5.34 3.56 175 44.50 24.92 18.32 12.46 8.31 6.23 4.15 200 50.86 28.48 20.94 14.24 9.49 7.12 4.75 225 57.21 32.04 23.56 16.02 10.68 8.01 5.34 250 63.57 35.60 26.18 17.80 11.87 8.90 5.93 Example 1: max. length at 1.5 mm2 and 3 A 214 m Example 2: max. length at 1.5 mm2 and 6 A 106 m Example 3: mixed wiring: R1 = 40 m in 1.5 mm2 and R2 = 5 m in 0.25 mm2: (Control cabinet – sensor/actuator level) R1 = 0.95 Ohm, R2 = 0.71 Ohm Total (R1 + R2) = 1.66 Ohm Electronic Circuit Protector ESX10 5 - 32 Issue C 5 Dimensions 12.3 operating area blade terminals DIN 46244-6.3-0.8 mounting area 60 10.3 70 50 6x6.8=40.8 6.8 reverse plug-in protection off 6A ok on 2.36 .405 2.75 .267 6x.267=1.60 1.97 .484 This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved. Product markings may not be exactly as the ordering codes. Errors and omissions excepted. ESX10 - Accessories: Module 17plus Issue C 5 - 33 5 ESX10-124 Modul 17 plus LINE (+) (1) GND (11) RE (13)