Megger MFT1731-OS Multifunction Tester - Onsite Bundle with Software Details
The complete package for professional electrical installers, this special onsite bundle package includes everything you'd get as standard with the Megger MFT1731 multifunction tester, plus additional accessories including Megger's Powersuite software and an earth spike kit to enable direct earth resistance testing.
Megger's MFT1731 is the most advanced model in Megger's multifunction tester series. With a huge range of testing functions, advanced safety features and fully downloadable memory (store up to 1000 results) it includes everything an electrical installer will need for testing low voltage installations in domestic, commercial and industrial properties.
With Megger's MFT1731 On-site package, you'll have everything you need for managing your test reports. Use this package to store/download results, download to PC, or even to allow multiple users to test different parts of the installation at the same time, then combine their results into one comprehensive testing report afterwards. You can even allow multiple users to complete the same certificate at different times, even if they're using different testers.
Every test you need can be performed with the MFT1731; this advanced test can perform insulation, continuity/resistance, loop, earth, RCD, voltage supply, leakage current and other measurements, ensuring you get fully comprehensive reports.
Megger MFT1731 Multifunction Tester Key Features
- Fully downloadable multifunction tester with integrated memory storage (store up to 1000 results)
- Bluetooth communication
- Insulation testing with selectable test voltages of 100, 250, 500 and 1000V + test voltage display and adjustable buzzer threshold
- Continuity/resistance test with 200mA and 15mA selection and adjustable buzzer threshold
- Loop testing - 2/3 wire non-tripping, 2 wire high current, 2 wire phase to phase, PSCC and PFC and Max Zs display
- Earth electrode test with 2 and 3 pole, 3 pole ART and stakeless methods available (requires optional accessory)
- RCD tests - 1/2, 5 x I, 1, ramp and Auto
- Suitable for use with multiple RCD types including AC, A, S, B (Pure DC) and programmable RCDs, plus 3-phase
- True RMS voltage supply measurements
- Leakage current measurements (requires optional clamp adaptor)
- Phase rotation indication
- Powered by fully rechargeable NiMH batteries
- CAT IV 300V and CAT III 600V safety rated
What's Included?
- Megger MFT1731-OS Multifunction Tester
- Printed Quick Start Guide
- Switched Probe
- Full User Guide on CD
- Calibration Certificate
- Megger Neck Strap
- 3 Wire Lead Set with Probes + Clips
- Mains Plug Test Lead (BS1363)
- AC Battery Charger
- Large Soft Carrying Pouch
- Powersuite Lite On-Site Mobile Software
- Earth Spike Kit
Megger MFT1711, MFT1721 and MFT1731 Technical Specifications
Please be aware that not all features are available for every model. If a feature is not included on a model, there will be a note next to each section.
Insulation Tests | |
Output Voltage | -0 to +20% at rated load or less |
Voltage Display | ±3% ±3 digits ±0.5% of rated voltage |
Short Circuit Current | 1.5mA nominal test current |
Test Current on Load | 1mA at min pass values of insulation |
Insulation Accuracy | |
1000V | 10kΩ to 999MΩ (±3% ± 2 digits) |
500V | 10kΩ to 500MΩ (±3% ± 2 digits) |
>500MΩ (±10% ± 4 digits) | |
250V | 10kΩ to 250Ω (±3% ± 2 digits) |
>250MΩ (±10% ± 4 digits) | |
100V | 10kΩ to 100MΩ (±3% ± 2 digits) |
>100MΩ (±10% ± 4 digits) | |
Resistance and Continuity | |
Range and Accuracy | 0.01 to 99.9Ω (±2% ± 2 digits) |
100 to 99.9kΩ (±5% ± 2 digits) | |
Open Circuit Voltage | 5V ± 1V |
Test Current (0 to 2Ω) | 205mA ±5mA |
15mA ±5mA (user selectable) | |
Loop Test | |
Live to Earth/Neutral Supply | 48 to 280V (45 to 65Hz) |
Live to Live Supply (Not Available on MFT1711) | 48 to 500V (45 to 65Hz) |
L-N/L-L Tests | ±5% ±5 digits |
L-E Tests | 0.1 to 39.9Ω (±5% ±5 digits ± noise margin) |
40Ω to 1000Ω (±10% ± 5 digits) | |
Display Range | 0.01 to 1000Ω |
Live to Earth PFC Range | 20kA |
Live to Live PSCC Range | 20kA |
RCD Tests | |
Supply up to 100mA | 48 to 480V (45 to 65Hz) |
Supply up to 1A | 48V to 280V |
RCD Type | Type AC, A and S |
Type B (Pure DC) | |
No-Trip Test (1/2xI) | -10 to -0% |
Trip Test (1xI, 2xI and 5xI) | +0 to +10% |
Ramp Test Touch Voltage (0 to 253V) | ±5% +15% ±0.5V |
Trip Time | ±1% ±1ms |
Trip Current | ±5% |
Step Increments | |
VAR (Variable RCD Selection) | |
10mA to 50mA | 1mA steps |
50mA to 500mA | 5mA steps |
500mA to 1000mA | 10mA steps |
Supply Measurement | |
Voltage | 10V to 600V (15 to 400Hz) True RMS |
Voltage Accuracy | ±3% ±1V ±2 digits |
Phase Rotation Indication | L1-L2-L3 and L1-L3-L2 |
Frequency | 15Hz to 99Hz (±0.5% ±1 digit) |
Frequency Resolution | 0.1Hz |
Power Supply | |
MFT1711 and MFT1721 | IEC LR6 type AA alkaline batteries |
MFT1731 | 1.2V NiMH Rechargeable Batteries Mains charger for on-board recharging (4 hours typical) 12V optional car charger available |
Earth/Ground Test (MFT1731 Only) | |
Resolution | 0.01Ω |
Current | 0.45mA or 4.5mA |
Noise Rejection | 20V pk/pk (7V rms) |
Max Probe Resistance (Rp and RC) | 100kΩ @ 50V |
5kΩ at 25V | |
2 and 3 Pole Method | 0.01 to 1.999kΩ (±2.0% ± 3 digits) |
ART method (1.00Ω to 1.999kΩ) with accuracy of ±5.0% ± 3 digits | |
Stakeless Method | 1.00 to 199Ω (±7.0% ± 3 digits) |
Current (Via Optional Clamp Meter) | |
Range | 0.1mA to 200A AC (5.0% ± 3 digits) |
Resolution | 0.1mA |
MV Sensor Input (MFT1721 and MFT1731) | |
Including Temperature | 0.0mV to ±199.9mV DC (±1.0% ± 2 digits) |
Resolution | 0.1mV |
Data Storage (MFT1731 Only) | |
Capacity | 1000 results |
Communication | Bluetooth |
Safety | |
IEC 61010-1: 2010 IEC 61010-30: 2010 IEC 61010-031: 2008 600V CAT III / CAT IV 300V (Max phase to phase 600V) IEC 61557: 2007 parts 1 to 10 |
|
EMC | IEC61326 edition 2 location class B |
Operating Temperature Range and Humidity | -10 to +55°C (90% RH at +40°C max) |
Storage Temperature Range and Humidity | -25 to +70°C |
Maximum Altitude | 2000m |
Weight (Instrument and Case) | 1kg (with batteries) |
Dimensions (Instrument and Case) - MFT1711 and MFT1721 | 150mm x 85 x 235mm (H x W x D) |
Dimensions (Instrument and Case) - MFT1731 | 220 x 390 x 285mm (H x W x D) |
IP Rating | IP54 |
Calibration Temperature | +20°C |
Temperature Coefficient | <0.1% per °C |