C.BREAKER TMAX XT3N 250 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 250-2500 A

Additional Information

Circuit Breaker Type to be Associated:
Power distribution
Electrical Durability:
120 cycles per hour
8000 cycle
Mechanical Durability:
Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
Number of Poles:
3
Opening Time:
CB with SOR 15 ms
CB with UVR 15 ms
Power Loss:
at Rated Operating Conditions per Pole 17.8 W
Product Main Type:
SACE Tmax XT
Product Name:
Moulded Case Circuit Breaker
Product Type:
CB
Rated Current (In):
250 A
Rated Frequency (f):
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp):
8 kV
Rated Insulation Voltage (Ui):
800 V
Rated Operational Voltage:
690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220 V AC) 37,5 kA
(220 V AC) 37,5 kA
(380 V AC) 27 kA
(415 V AC) 27 kA
(440 V AC) 18,75 kA
(500 V AC) 15 kA
(690 V AC) 3,75 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(220 V AC) 50 kA
(230 V AC) 50 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 25 kA
(500 V AC) 20 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 36 kA
(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu):
250 A
Rated Voltage (Ur):
690 V
Release Type:
TM
Standards:
IEC
Sub-type:
XT3
Terminal Connection Type:
Fixed Circuit-Breakers
Front
  • Version:
    F