GEYA RCCB Auto Recloser/Auto Reclosing Device Coupled With RCCB

Product Description

Please check this before you buy this item!

We have 4 different type of Recloser.

1.GRD9L-C= Recloser is Swicth Input Control Mode

2.GRD9L-D= Recloser is Controlled by switch+Auto Reclosing

3.GRD9L-S= Recloser is RS485 Control Mode,(Connect with Computer or PLC)

4.GRD9L-R= Recloser is Auto Reclose Control Mode

This link is for GRD9L-R,If you need other type,Please contact me !


Applications

Can be widely used in power grid terminal line, such as meter box,new energy circuit management, PV solar control box, smart electricity, smart home, new energy vehicle charging pile, and so on.

Function Features

1. It is coupled with leakage protection switch and automatically reclose when RCCB trips unexpectedly. No need for manual closing, reduce the cost of manual maintenance, and eliminate faults in time to improve efficiency.

2. Builted in 3 reclosing times. If continuous closing failure within 15 minutes, it can send alarm through auxiliary contact.

3. With manual / automatic selector switch.

4. With mechanical / electronic double locking function.

5. Can match Auxillary contact, Alarm contact,Shunt release,Under voltage release

6. Work status is indicated by LED.

7. Reset the closing times, When no trip or manual reset within 15 minutes after successful closing

Technical parameters GRD9L-R
Control mode auto reclosing
Voltage range AC 230V(50-60Hz)
Power input AC max.1VA(standby) max.20VA(action)
Supply voltage tolerance -10%;+10%
Action time ≤1s
Auto reclosing times 3
Auto reclosing interval time 10s-60s-300s
Mechanical life 10000
Electrical life(AC1) 4000
Operating temperature  -20℃ to +55℃(-4℉ to 131℉)
Mounting/DIN rail Din rail EN/IEC 60715
Max.cable size(mm2) solid wire max.1×2.5 or 2×1.5/ with sleeve max.1×2.5(AWG 12)
Dimensions 82×18×78mm
Combination with accessories Auxillary contact, Auxillary contact, Shunt release, Under voltage release

Technical parameters RCCB
Rated Current In 40A 63A
Poles 2P
Rated Voltage Ue 230V~
Insulation voltage Ui 500V
Rated frequency 50/60Hz
Rated Sensitivity I△n 30mA, 300mA
Electrical Life 4000
Mechanical Life 8000
Ambient temperature  -5~+40℃
Terminal connection type Cable/U-type busbar/Pin-type busbar
Terminal size top/bottom for cable 35mm2 18-3
Tightening torque 3.5 N*m 22


Common faults

Fault description Resolvent
1 Unable to close or open 1、Please confirm whether the power supply voltage is normal.
2、Please confirm whether the working mode is set in AUTO mode.
3、Please confirm the buckle of the electric operation mechanism and MCB / RCCB.
2
Trip immediately after
closing
1、Please check the circuit to confirm whether there is overload / short circuit / leakage fault at the lower end of MCB / RCCB.
2、Whether the circuit breaker is damaged or not, and whether it is slipped.


More Type for your consider

Model Pole Link
Self-Reclosing MCB 1P https://www.ebay.com/itm/115295504398
2P https://www.ebay.com/itm/115439440560
3P https://www.ebay.com/itm/115439563200
4P https://www.ebay.com/itm/115439614957
Self-Reclosing RCCB 2P https://www.ebay.com/itm/114467876721
4P https://www.ebay.com/itm/113782800787
We only accept payment via Paypal at present.  If you want to pay by other method, please contact me.

We will process your order within 1 business day upon payment except holidays and weekends. Once I update tracking number, orders can not be canceled. 


Economy shipping:

all economy shipping parcels dnot comwith tracking information or only provide tracking information when parcels are in China. If you haven't recieved your parcels after wait a long time, please contact your local post office to check your parcel by providing your recipient's name and mobile phone number. 


Standard shipping:

standard shipping parcels provide whole tracking information. Suggested!


Expedited shipping:

If you need expedited shipping service, please contact me. 

Please read the item description and check the pictures carefully before making orders. Return or refund is available if:
 
1. The item was damaged in transit.
2. Product quality problem.
 

When you submit a return or refund application, please 

1. Provide a detailed problem description and photos so that we can deal with it as soon as possible. 

2. Please obey my requirments about packing of return goods. After warehouse staff recieve and check your parcel is ok, then I will refund you.


DataCaciques