Manufacturer: Liebert
Model: Liebert GXT5 3000VA 2700W, RM, 2U, 120V
Condition: New batteries, refurbished UPS
Part Number: GXT5-3000LVRT2UXL
Maximum output: 2700W / 3000VA
Typical backup time at half load: 9 minutes (1350 Watts)
Typical backup time at full load: 3 minutes (2700 Watts)
Warranty: 1 year full replacement warranty
Liebert GXT5 3000VA 2700W RM 2U GXT5-3000LVRT2UXL User's Manual
GXT5-3000LVRT2UXL - Liebert GXT5 3000VA Specifications:
Product Overview:
Power Rating |
3000VA / 2700W |
Input Voltage |
Typical: 120V / Range: 60-150V |
Output Voltage |
110/115/120/125VAC; (user-configurable); ±3% |
Efficiency |
Up to 98% Active ECO Mode; up to 95% on-line mode |
Wiring |
Input: NEMA L5-30P; Output: L5-30R+5-20R × 6 |
Interfaces/Ports:
Interface Options |
Optional communications card (Vertiv RDU101), USB, RS485, RS232, terminal block, external battery connector |
Protocols |
SNMP and web management enabled with optional Vertiv RDU101 communications card; serial connection for out-of-band management |
Control Panel |
Colored graphic LCD with gravity sensing orientation, provides insight to UPS status for easy installation, configuration and operation |
Operational Conditions:
Operating Temperature |
+32 to +104 °F (0 to 40 °C) |
Miscellaneous:
General |
Output Receptacles: 1 x L5-30R + 5-20R × 6; 4 x 5-20R individually programmable receptacles and 1 x L5-30R and 2 x 5-20R non-programmable receptacles |
Listings |
ENERGY STAR 2.0 certified, WEEE, RoHS2, REACH, UL 1778 4th edition and CSA 22.2 No. 107.1 |
Topology |
On-line double conversion UPS; compact and flexible rack/tower form factor |
Dimensions, D×W×H, in. (mm):
Unit |
21.3 x 16.9 x 3.4 (540 x 430 x 85) |
Weight, lb.(kg):
Unit |
66 (30) |
Input AC:
Voltage Range (typical) |
120 VAC nominal, variable based on output load |
90% ~ 100% loading |
94 ~ 102 VAC/149.5 VAC |
70% ~ 90% loading |
77 ~ 94 VAC/149.5 VAC |
50% ~ 70% loading |
60 ~ 77 VAC/149.5 VAC |
0% ~ 50% loading |
60 VAC/149.5 VAC |
Frequency |
40 Hz ~ 70 Hz; auto-sensing |
Input Power Cord |
10-ft. (3 m) attached with NEMA L5-30P plug |
Output AC:
Output Receptacles |
L5-30R + 5-15/20R x 6 |
Voltage |
100/110/115/120/125 VAC (user-configurable); ±3% |
Waveform |
Sine wave |
Normal Mode Overload |
> 200% for 250 mS |
Battery Parameters:
Type |
Valve-regulated, non-spillable, lead acid |
Quantity x Voltage x Rating |
6 x 12V x 9.0Ah |
Battery Mfr./Part # |
LEOCH DJW12-9.0 |
Recharge Time |
3 hours to 90% capacity after full |
Environmental:
Operating Temperature, °F (°C) |
32 to 122 (0 to 50) |
Storage Temperature, °F (°C) |
–4 to 140 (–20 to 60) [batteries are from 5 to 104 (–15 to 40)] |
Relative Humidity |
0% – 95% non-condensing |
Operating Elevation |
Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating |
Audible Noise |
<46 dBA max. at 3 ft (1 m) front and sides, <48 dBA max. at 3 ft (1 m) rear |