Manufacturer: Liebert
Model:
 Liebert GXT5 3000VA 2700W, RM, 2U, 120V
Condition:
New batteries, refurbished UPS
Part Number:
GXT5-3000LVRT2UXL

Maximum output: 2700W / 3000VA
Typical backup time
at half load: 9 minutes (1350 Watts)
Typical backup time
at full load: 3 minutes (2700 Watts)
Warranty:
1 year full replacement warranty


Liebert GXT5 3000VA 2700W RM 2U GXT5-3000LVRT2UXL User's Manual


GXT5-3000LVRT2UXL - Liebert GXT5 3000VA Specifications:

Product Overview:

Power Rating

3000VA / 2700W

Input Voltage

Typical: 120V / Range: 60-150V

Output Voltage

110/115/120/125VAC; (user-configurable); ±3%

Efficiency

Up to 98% Active ECO Mode; up to 95% on-line mode

Wiring

Input: NEMA L5-30P; Output: L5-30R+5-20R × 6


Interfaces/Ports:

Interface Options

Optional communications card (Vertiv RDU101), USB, RS485, RS232, terminal block, external battery connector

Protocols

SNMP and web management enabled with optional Vertiv RDU101 communications card; serial connection for out-of-band management

Control Panel

Colored graphic LCD with gravity sensing orientation, provides insight to UPS status for easy installation, configuration and operation


Operational Conditions:

Operating Temperature

+32 to +104 °F (0 to 40 °C)


Miscellaneous:

General

Output Receptacles: 1 x L5-30R + 5-20R × 6; 4 x 5-20R individually programmable receptacles and 1 x L5-30R and 2 x 5-20R non-programmable receptacles

Listings

ENERGY STAR 2.0 certified, WEEE, RoHS2, REACH, UL 1778 4th edition and CSA 22.2 No. 107.1

Topology

On-line double conversion UPS; compact and flexible rack/tower form factor


Dimensions, D×W×H, in. (mm):

Unit

21.3 x 16.9 x 3.4 (540 x 430 x 85)


Weight, lb.(kg):

Unit

66 (30)


Input AC:

Voltage Range (typical)

120 VAC nominal, variable based on output load

90% ~ 100% loading

94 ~ 102 VAC/149.5 VAC

70% ~ 90% loading

77 ~ 94 VAC/149.5 VAC

50% ~ 70% loading

60 ~ 77 VAC/149.5 VAC

0% ~ 50% loading

60 VAC/149.5 VAC

Frequency

40 Hz ~ 70 Hz; auto-sensing

Input Power Cord

10-ft. (3 m) attached with NEMA L5-30P plug


Output AC:

Output Receptacles

L5-30R + 5-15/20R x 6

Voltage

100/110/115/120/125 VAC (user-configurable); ±3%

Waveform

Sine wave

Normal Mode Overload

> 200% for 250 mS
150 – 200% for 2 seconds
125 – 150% for for 10 seconds
105 – 125% for 15 seconds


Battery Parameters:

Type

Valve-regulated, non-spillable, lead acid

Quantity x Voltage x Rating

6 x 12V x 9.0Ah

Battery Mfr./Part #

LEOCH DJW12-9.0

Recharge Time

3 hours to 90% capacity after full
discharge with 100% load til UPS autoshutdown (internal batteries only)


Environmental:

Operating Temperature, °F (°C)

32 to 122 (0 to 50)

Storage Temperature, °F (°C)

–4 to 140 (–20 to 60) [batteries are from 5 to 104 (–15 to 40)]

Relative Humidity

0% – 95% non-condensing

Operating Elevation

Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating

Audible Noise

<46 dBA max. at 3 ft (1 m) front and sides, <48 dBA max. at 3 ft (1 m) rear