Manufacturer: Vertiv
Model: Vertiv Liebert GXT5 8000VA 8000W RM/Tower 5U 208V/240V - Online Double Conversion UPS

Condition: New batteries, refurbished UPS
Part Number: GXT5-8000HVRT5UXLN
Maximum output:
 8000W / 8000VA
Typical backup time
at half load: 9.5 minutes (4000 Watts)
Typical backup time
at full load: 3.5 minutes (8000 Watts)
Warranty:
1 year full replacement warranty
Included: UPS, rack ears, rail kit, tower stand (feet), USB cable


Vertiv Liebert GXT5 8000VA 8000W 208V/240V GXT5-8000HVRT5UXLN User's Manual

 


GXT5-8000HVRT5UXLN - Vertiv UPS 8000VA / 8000W Specifications:


Overview:

Power Rating

8,000VA / 8,000W

Input Voltage

Typical: 208VAC / Range: 176-288VAC - L1-L2-G

Output Voltage

200/208/220/230/240 VAC (user-configurable)

Efficiency

Up to 98% Active ECO Mode; up to 95% on-line mode

Wiring

Hardwired in/out + Output: 2 x L6-20R, 2 x L6-30R


Operational Conditions:

Operating Temperature

+32 to +104 °F (0 to 40 °C)


Physical:

Dimensions (inch/mm)

16.9 × 24.8 × 8.5 (430×630×217)

Weight (lbs/kg)

75.5 (166.4)


Input AC:

Operating Frequency, Nominal

50 or 60 Hz (factory-default is 60 Hz)

Factory-default VAC

208 VAC - L1-L2-G

User-configurable VAC

200/208/220/230/240 VAC
(Adjustable using operation/display configuration options)

Operating voltage range without battery operation

176 – 288 VAC (100 – 176VAC with power derating)

Maximum Allowable VAC

288 VAC

Input Frequency without Battery Operation

40 – 70 Hz

Input Power Connection

PD5-CE10HDWRMBSU


Output AC:

Output Receptacles

(2) NEMA L6-20R

(2) NEMA L6-30R

Hardwired in/out

 

AC-AC Efficiency

95%

Factory-default VAC Frequency

208 VAC, 60 Hz

Output Voltage

208 VAC Nominal
Adjustable to 200/220/230/240 VAC

Output Power Connection

PD5-CE10HDWRMBSU

Waveform (on battery)

Sine wave

Utility (AC) Mode Overload

>150% minimum 200 mS,
125 – 150% for 60 seconds;
105 – 125% for for 5 minutes;
≤ 105% continuous


Interfaces / Ports:

Interface Options

Optional Vertiv™ IS-UNITY-DP SNMP/Webcard, USB, RS485, RS232, terminal block, external battery connector

Protocols

SNMP and web management enabled with Optional Vertiv IS-UNITY-DP communications card; serial connection for out-of-band management

Control Panel

Full-color graphic LCD with gravity sensing orientation, provides insight to UPS status for easy installation, configuration and operation


Internal Battery Charger:

Charger Current, A

2.25A default, maximum 8A


Battery Parameters:

Type

Valve-regulated, non-spillable, lead acid

Quantity x Voltage x Rating

16 x 12V x 9.0AH

Backup Time (100% Load)

3.5 Minutes

Backup Time (50% Load)

9.5 Minutes

+1 External Battery Cabinet (100% Load)

9.5 Minutes

+1 External Battery Cabinet
(50% Load)

26 Minutes

Upper-limit selections

+10%, +15%, +20%; default +10%.

Lower-limit selections

-10%, -15%, -20%; default -15%

Disable-bypass operation

When the input frequency prevents synchronous operation


Environmental:

Operating Temperature, °F (°C)

+32 to +104 (0 to 40)
(no derating)

Storage Temperature, °F (°C )

5 to 104 (–15 to 40)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating

Audible Noise

<55 dBA,at 1 meter from the front,
<50 dBA, at 1 meter from rear
or sides


Agency:

Safety

IEC62040-1:2008 version, 
GS mark;
UL1778, c-UL listed

EMI/EMC/C-Tick EMC

IEC/EN/AS 62040-2 2nd
Ed (Cat 2 – Table 6); FCC Part 15 (Class A)
CISPR22 Class A (RFI)

ESD

IEC/EN EN61000-4-2, 
Level 4, Criteria A

Radiated Susceptibility

IEC/EN EN61000-4-3, 
Level 3, Criteria A

Electrical Fast Transient

IEC/EN EN61000-4-4, 
Level 4, Criteria A

Surge Immunity

IEC/EN EN61000-4-5,
Level 4, Criteria A;
ANSI C62.41 Category B

Transportation

ISTA Procedure 1E

Emissions

FCC Part 15 (Class A)


Miscellaneous:

Listings

ENERGY STAR® 2.0 certified, UL1778, c-UL listed, RoHS2, REACH

Topology

On-line double conversion UPS; flexible rack/tower form factor