Features
Voltage Regulation < ± 1%
Drive Infrared LED to Control Excitation
50/60 Hz Optional
Under Frequency Protection
Adjustable Stability
External Voltage Trimmer Applicable
Specifications
Sensing Input Voltage 220 VAC 1 phase 2 wire
Frequency 50/60 Hz select by jumper
Power Input Voltage 10~26 VDC
Output Current 20 Amp
Volts Regulation < ±1% (with 4% engine governing)
External Volts Adjustment ±10% with 1 K Ohm 1 watt trimmer
Unit Power Dissipation Max. 2 watt
Thermal Drift 0.05% per °C change in AVR ambient
Under Frequency Protection
(Factory Setting) 60 Hz system presets knee point at 55 Hz
50 Hz system presets knee point at 45 Hz
Environment Operating Temperature : -40~65 °C
Storage Temperature : -40~80 °C
Relative Humidity : Maximum 95%
Vibration : 3.3G @ 100~2 KHz
AVR Controls Functions STAB : Stability Adjustment
Dimensions 127.2 (L) x 141.5 (W) x 39.0 (H) mm
Weight 109g ±2%