Notice: Many models of the Gulf have been upgraded. The original smoke model JTY-GD-G3 has been upgraded to JTY-GD-G3T. The G3 smoke has been discontinued. The new G3T is fully compatible with the old G3 smoke.
parameter:
Working voltage: bus 24V
Monitoring current: ≤0.8mA
Alarm current: ≤1.8mA
Alarm confirmation light: red, flashing during inspection, always on when alarm
Temperature: -10 ° C ~ +55 ° C
Relative humidity: ≤95%, no condensation
Coding method: decimal electronic coding
Shell protection rating: IP23
Diameter: 100mm
Height: 54mm (with base)
When the space height is 6m~12m, the protection area of one detector is 80m2 for general protection places. When the space height is 6 m or less, the protection area is 60 m2. The specific parameters shall be subject to the "Code for Design of Automatic Fire Alarm System" (GB 50116).
 
feature: