New M170 Generator Controller 8-35V DC Replace

HGM170 HC


SPECIFICATION:

  • DC Supply: 8 to 35 V DC continuous.
  • Alternator Input Range: 15-300 VAC(+20%) RMS
  • Alternator Input Frequency: 50-60 Hz at rated engine speed.
  • Over speed: nominal frequency +14% (+24% Overshoot)
  • Start Output: Relay 1A plant battery negative B - terminal
  • Fuel Output: Relay 1A plant battery negative B - terminal
  • Pre-heat Output: Relay 1A plant battery negative B - terminal
  • Stop Output: Relay 1A plant battery negative B - terminal
  • Four switch Inputs: Switch to negative.
  • Frequency select: Select 50Hz or 60Hz nominal

Fixed Settings 

  • Crank Disconnect : Generator voltage ≥ 15VAC frequency ≥ 15Hz
  • Charge Failure Voltage: ≤ 3V
  • Remote start delay: 2seconds
  • Crank period: 5 seconds
  • Crank rest : 10seconds
  • Safety delay: 10seconds
  • Remote stop delay: 10seconds
  • Case Dimensions: 84mm x 72mm x 3 5mm
  • Operating Temperature Range: -30 to +70°C