Features
Mini-sized and integrated temperature control
can directly control 1HP compressor (include 1HP)
Temperature display/Temperature control
Manual, automatically defrost/
Evap. fan control/ Time, temperature setting to end defrost
Energy saving mode/
Light control/Value storing
Parameter locking/ Self testing
Technical Data
Temperature display range: -45~66℃(-45~150℉)
Set temperature range:-40℃~45℃(-40~113℉)
Accuracy:±1℃(1℉)
Temperature sensor: NTC, two sensors, 2 meters (Neither positive nor negative ,white)
Compressor :N.O. 30A/250VAC (can directly connect to 1HP compressor, if more needs
to connect an AC contactor)
Defrost heater: N.O. 8A/250VAC (can directly connect to 1KWload, if more needs to
connect an AC contactor)
Evap. fan: N.O.5A/250VAC Lihgt: N.O.5A/250VAC
Increase dor (condenser sensor, door switch, alarminput) model
Dimension:77 L mm*35(W)mm*70(D)mm
Mounting hole dimension: 71mm L*29mm(W)
Parameters
Parameter | Function | Set range | Default |
PAS | Password | 00~99 | 15 |
E1 | Lowest set point limit | -40℃ -40℉~set temp. | -25℃ -13℉ |
E2 | Higher set point limit | set temp.~45℃ 113℉ | 20℃ 68℉ |
E3 | Hysteresis | 01~20℃ 02~36℉ | 04℃ 07℉ |
E40 | Comp. start delay time | 00~10min | 2min |
E41 | Delay starting time | 00~10min | 2min |
E5 | Offset on room temp. | -20~20℃ -36~36℉ | 00℃ 00℉ |
E6 | Offset on evap. temp. | -20~20℃ -36~36℉ | 00℃ 00℉ |
E7 | Offset on condenser temp. | -20~20℃ -36~36℉ | 00℃ 00℉ |
F0 | Defrost type | 00=defrost by turning off comp. 01=he ting defrost 02=hot gas defrost | 01 |
FF0 | When enter hot gas defrost comp. delay starting time | 00~20min | 00min |
FF1 | Defrost interval way | 00=power on time 01=comp. continuously working time | 00 |
F1 | Maxdefrost duration | 01~60min | 20min |
F2 | Defrost interval | 00~24Hr | 6Hr |
F30 | Defrost starting temperature | -40℃ -40℉~F31 | 00℃ 32℉ |
F31 | Defrost termination temperature | F30~40℃ 104℉ | 08℃ 46℉ |
F4 | Display during defrost | 00=normal display 01=last value before defrost 02=dEF | 00 |
F5 | Dripping time | 00~30min | 2min |
P1 | Fan control during refrigeration | 00=synchronized with compressor 01=keep running 02=determined by P4 , P5 | 00 |
P2 | Fan control during defrost | 00=off 01=on 02=determined by P4, P5 | 00 |
P3 | Fan operating way after defrost | 00=time (P6) 01=determined by P4, P5 | 00 |
P4 | Fan starting temperature (evap. Sensor lower than starting) | -30℃ -22℉~P5 | 10℃ 50℉ |
P5 | Fan termination temperature (evap.Sensor higher than starting ) | P4~30℃ 86℉ | 25℃ 77℉ |
P6 | Fan delay starting time after defrost | 00~30min | 2min |
C1 | Cold room high temperature alarm | C2~45℃ 113℉ | 40℃ 104℉ |
C2 | Cold room low temperature alarm | -40℃ -40℉~C1 | -40℃ -40℉ |
C3 | Condenser high temperature alarm | -40℃~100℃ -40℉ 212℉ | 45℃ 113℉ |
C4 | Alarm hysteresis | 01~20℃ 02~36℉ | 02℃ 04℉ |
C5 | Outer alarm input effective work way | 00=comp. stop running 01=running as C7, C8 | 00 |
C6 | Alarm delay | 00~99min | 2min |
C7 | Comp. force stop time | 01~99min | 10min |
C8 | Compressor force running time | 00=comp. stop running 01~99min=starting time | 30min |
C9 | Alarm output type | 00=contact actuation when alarm 01=contact disconnection when alarm | 00 |
CF | Temperature unit | ℃=Celsius ℉=Fahrenheit | ℃ |
d1 | Display type | 00=display current actual cold room temp. 01=display no more than set temp.+E3+d2 02=fixed display set temperature | 00 |
d2 | Display increment | 01~30℃ 01~54℉ | 05℃ 09℉ |
dor | Input type | 01=condensersensor 02=doorswitch (door open contact actuation) 03=doorswitch (door open contact disconnected) 04=alarminput (contact disconnect alarm) 05=alarminput (contact actuation alarm) | 02 |
do1 | Door open over time alarm | 00~30min | 5min |
do2 | Fan status when door open | 00=stop 01=original status | 00 |
do3 | Light status when door open | 00=start 01=original status | 00 |
do4 | Temperature display when door is open | 00=normal display 01~99=locked display time | 5min |
L1 | Door open energy saving mode | 00=close 01=start (when dor=2, 3 effective) | 00 |
L2 | Energy saving trigger time | 01~20Hr (continuous door not open time) | 2Hr |
L3 | Energy saving control temperature increment | 00~20℃ 00~36℉ | 05℃ 09℉ |
L4 | Exit energy saving mode | 01~05times | 01times |