SF-406 Chiller electronic intelligent 220v defrost blue digital display temperature controller

Product Description

SF-406 drinks cabinet refrigeration digital blue display temperature controller with fan relay

 

Features

Mini-sized and integrated temperature control

can directly control 1HP compressor (include 1HP)

Temperature display/Temperature control

Manual, automatically defrost/

Evap. fan control/ Time, temperature setting to end defrost

Energy saving mode/

Light control/Value storing

Parameter locking/ Self testing

 

Technical Data

Temperature display range: -45~66℃(-45~150℉)

Set temperature range:-40℃~45℃(-40~113℉)

Accuracy:±1℃(1℉)

Temperature sensor: NTC, two sensors, 2 meters (Neither positive nor negative ,white)

Compressor :N.O. 30A/250VAC (can directly connect to 1HP compressor, if more needs

to connect an AC contactor)

Defrost heater: N.O. 8A/250VAC (can directly connect to 1KWload, if more needs to

connect an AC contactor)

Evap. fan: N.O.5A/250VAC Lihgt: N.O.5A/250VAC

Increase dor (condenser sensor, door switch, alarminput) model

Dimension:77 L mm*35(W)mm*70(D)mm

Mounting hole dimension: 71mm L*29mm(W)

 

Parameters

ParameterFunctionSet rangeDefault
PAS
Password
00~99
15
E1 Lowest set point limit

-40

-40~set temp.

 -25℃
-13℉
E2 Higher set point limit
set temp.~45
113
 20℃
68℉
E3 Hysteresis 01~20℃
02~36℉
04℃
07℉
E40 Comp. start delay time
00~10min
2min
E41 Delay starting time 00~10min2min
E5 Offset on room temp.
-20~20℃
-36~36℉
00℃
00℉
E6 Offset on evap. temp.
-20~20℃
-36~36℉
00℃
00℉
E7 Offset on condenser temp. -20~20℃
-36~36℉
00℃
00℉
F0 Defrost type
00=defrost by
turning off comp.
01=he ting defrost
02=hot gas defrost
01 
FF0 When enter hot gas defrost comp. delay starting time
00~20min
00min
FF1 Defrost interval way
00=power on time
01=comp. continuously working time
00
F1
Maxdefrost duration
01~60min20min
F2 Defrost interval00~24Hr6Hr
F30 Defrost starting temperature

-40

-40~F31

 00℃
32℉
F31Defrost termination temperature

 F30~40

104

08℃
46℉
F4 Display during defrost
00=normal display
01=last value before defrost
02=dEF
00
F5 Dripping time00~30min2min
P1 Fan control during refrigeration 00=synchronized
with compressor
01=keep running
02=determined by P4 , P5
00
P2 Fan control during defrost 00=off
01=on
02=determined by P4, P5
00
P3 Fan operating way
after defrost
00=time (P6)
01=determined by P4, P5
00
P4 Fan starting temperature
(evap. Sensor lower than starting)

 -30

-22~P5

10℃
50℉
P5 Fan termination temperature
(evap.Sensor higher than starting )

P4~30

86

25℃
77℉
P6
Fan delay starting time after defrost
00~30min
2min
C1 Cold room high temperature alarm

C2~45

113

40℃

104℉
C2 Cold room low temperature alarm

 -40

-40~C1

-40℃
-40℉
C3 Condenser high temperature alarm

 -40~100

-40   212

45℃
113℉
C4 Alarm hysteresis 01~20℃
02~36℉
02℃
04℉
C5Outer alarm input effective work way

00=comp. stop running

01=running as C7, C8

00
C6 Alarm delay
00~99min
2min
C7 Comp. force stop time
01~99min
10min
C8 Compressor force running time

00=comp. stop running

01~99min=starting time

30min
C9 Alarm output type00=contact actuation when alarm
 01=contact disconnection whealarm
00
CF Temperature unit ℃=Celsius ℉=Fahrenheit
d1 Display type
00=display current actual cold room temp.
01=display no more than set temp.+E3+d2
02=fixed display set temperature 
00
d2 Display increment
01~30℃ 
01~54℉
05℃
09℉
dor Input type
01=condensersensor
02=doorswitch (door open contact actuation)
03=doorswitch (door open contact disconnected) 
04=alarminput (contact disconnect alarm)
05=alarminput (contact actuation alarm)
02
do1 Door open over time alarm
00~30min
5min
do2 Fan status when door open 00=stop
01=original status
00
do3 Light status when door open
00=start
01=original status
00
do4 Temperature display when door is open 00=normal display
01~99=locked display time
5min
L1 Door open energy saving mode
00=close
01=start (when dor=2, 3 effective)
00
L2
Energy saving trigger time 
01~20Hr
(continuous door not open time)
2Hr
L3 Energy saving control temperature increment00~20℃
00~36℉
05℃
09℉
L4 Exit energy saving mode01~05times01times

 

SF-406 drinks cabinet refrigeration digital blue display temperature controller with fan relay