range |
TeSys |
---|---|
product or component type |
Contactor |
product name |
TeSys K |
device short name |
LC1K |
device application |
Control |
contactor application |
Motor control |
utilisation category |
AC-3 AC-4 |
|
---|---|---|
poles description |
3P |
|
pole contact composition |
3 NO |
|
[Ue] rated operational voltage |
Power circuit: 690 V AC 50/60 Hz Signalling circuit: <= 690 V AC 50/60 Hz |
|
[Ie] rated operational current | 6 A at <= 440 V AC AC-3 for power circuit |
|
control circuit type |
AC at 50/60 Hz |
|
[Uc] control circuit voltage |
110 V AC 50/60 Hz |
|
motor power kW |
1.5 kW at 220...230 V AC 50/60 Hz AC-3 2.2 kW at 380...415 V AC 50/60 Hz AC-3 3 kW at 440 V AC 50/60 Hz AC-3 3 kW at 480 V AC 50/60 Hz AC-3 3 kW at 500...600 V AC 50/60 Hz AC-3 3 kW at 660...690 V AC 50/60 Hz AC-3 1.5 kW at 400 V AC 50/60 Hz AC-4 |
|
auxiliary contact composition |
1 NC |
|
[Uimp] rated impulse withstand voltage |
8 kV |
|
overvoltage category |
III |
|
[Ith] conventional free air thermal current |
20 A at <= 122 °F (50 °C) power circuit 10 A at <= 122 °F (50 °C) signalling circuit |
|
Irms rated making capacity |
110 A AC power circuit conforming to NF C 63-110 110 A AC power circuit conforming to IEC 60947 110 A AC signalling circuit conforming to IEC 60947 |
|
rated breaking capacity |
110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947 |
|
[Icw] rated short-time withstand current |
90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit |
|
associated fuse rating |
25 A gG at <= 440 V power circuit 25 A aM for power circuit 10 A gG for signalling circuit conforming to IEC 60947 10 A gG for signalling circuit conforming to VDE 0660 |
|
average impedance |
3 mOhm - Ith 20 A 50 Hz for power circuit |
|
[Ui] rated insulation voltage |
Power circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-5-1 Signalling circuit: 600 V conforming to UL 508 Power circuit: 600 V conforming to CSA C22.2 No 14 Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
|
insulation resistance |
> 10 MOhm signalling circuit |
|
inrush power in VA |
30 VA at 68 °F (20 °C) |
|
hold-in power consumption in VA |
4.5 VA at 68 °F (20 °C) |
|
heat dissipation |
1.3 W |
|
control circuit voltage limits |
0.2...0.75 Uc at <= 122 °F (50 °C) drop-out 0.8...1.15 Uc at <= 122 °F (50 °C) operational |
|
connections - terminals |
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1.5…4 mm²solid Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
|
maximum operating rate |
3600 cyc/h |
|
auxiliary contacts type |
Type instantaneous (1 NC) |
|
signalling circuit frequency |
<= 400 Hz |
|
minimum switching current |
5 mA for signalling circuit |
|
minimum switching voltage |
17 V fpr signalling circuit |
|
mounting support |
Rail Plate |
|
tightening torque |
1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm |
|
operating time |
10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing |
|
safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
non overlap distance |
0.02 in (0.5 mm) |
|
mechanical durability |
10 Mcycles |
|
electrical durability |
1.3 Mcycles 6 A AC-3 at Ue <= 440 V |
|
mechanical robustness |
Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6 |
|
height |
58 mm |
|
width |
45 mm |
|
depth |
57 mm |
|
net weight |
0.18 kg |
standards |
BS 5424 IEC 60947 NF C 63-110 VDE 0660 |
---|---|
product certifications |
UL CSA |
product certifications |
IP2x conforming to VDE 0106 |
protective treatment |
TC conforming to IEC 60068 TC conforming to DIN 50016 |
ambient air temperature for storage |
-50…80 °C |
operating altitude |
6561.68 ft (2000 m) without derating in temperature |
flame retardance |
V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
You can pick up from Fullerton, California or Piscataway, New Jersey or we will ship via UPS Ground.
Contact us for exact shipping cost.
Payment
Supra Machine Tool accepts: PayPal, Visa, Master Card, American Express, Money Orders, Cashier Checks, Wire Transfer as payment of goods purchased in our store. (Please send payment to 2320 E Valencia Dr Fullerton, CA 92831) All payments must be received within 7 business days. All buyers residing in California add 8.75% sales tax.
Shipping and Handling
Buyer pays the Shipping charge based on USPS Priority Mail or UPS Ground Shipping Charges. Orders being shipped to P.O. Boxes will be delivered by United States Postal Services (USPS). Note: Weight restrictions may apply in some cases. Orders under 150 lbs. can be shipped by U.P.S., freight prepaid or collect. Orders above 150 lbs. will be shipped by freight carrier. Supra Machine Tool offers a group of carriers that can quote you with an estimate of shipping charges for all items. Estimated delivery time by UPS is from 2 to 6 business days from the time the order is processed. International buyer pays the actual shipping charge + $5.50-$7.50 handling fees. International shipments of 150 lbs or more can be made by UPS International. Buyers are responsible for payment of all Shipping and Handling charges on all items.
Terms and Conditions
We guarantee the items are exactly as said in description. If you do not pay for them in the specified amount of time we have to file a non-paying complaint with eBay. Thank you for viewing. Supra Machine Tool appreciates your business very much.