Supply voltage
- Load voltage L+
- Rated value (DC): 120 V
Load voltage L1
Input current
- from backplane bus 5 V DC, max.: 100 mA
Power losses
Digital outputs
- Number/binary outputs: 16 ; Relay
- Lamp load, max.: 50 W ; 230 V AC
Output current
- for signal "1" rated value: 2 A
- for signal "1" minimum load current: 10 mA
Switching frequency
- With resistive load, max.: 1 Hz
- With inductive load, max.: 0.5 Hz
- On lamp load, max.: 1 Hz
- Mechanical, max.: 10 Hz
Aggregate current of outputs (per group)
- Horizontal installation, up to 60 °C, max.: 8 A
- Vertical installation, up to 40 °C, max.: 8 A
Relay Outputs
- Rated input voltage of relay coil L+ (DC): 24 V
- Number of operating cycles, max.: 100000 ; 50000 (24 V DC, at 2 A); 700000 (120 V AC, at 2 A); 100000 (230 V AC, at 2 A);
Switching Capacity of Contacts
- With inductive load, max.: 2 A ; 2 A (230 V AC), 2 A (24 V DC)
- Switching frequency / contacts / at ohmic load / maximum: 2 A ; 2 A (230 V AC), 2 A (24 V DC)
Cable Length
- Cable length, shielded, max.: 1000 m
- Cable length unshielded, max.: 600 m
Interrupts / Diagnostics / Status Information
Alarms
Diagnostic Messages
- Diagnostics: No
- Wire break: No
- Short circuit: No
- Fuse blown: No
- Missing load voltage: No
Diagnostics Indication LED
- Rated load voltage PWR (green): No
- Fuse OK FSG (green): No
Galvanic Isolation
- Galvanic isolation digital outputs
- Between the channels, in groups of 8
- Between the channels and the backplane bus: Yes ; Optocoupler
Isolation
- Isolation checked with: 1500 V AC
Connection Method
- Required front connector: 20-pin
Dimensions
- Width: 40 mm
- Height: 125 mm
- Depth: 120 mm
Weight