INPUT
Voltage190-264VAC
Frequency50-60HZ nominal
Phase1
Wire2
OUTPUT
Voltagemax 90DC at 207VAC input
Correntcontinuous 4A dc
Intermittent 6A for 10 secs
Resistance15ohms minimum
REGULATION
±1%(see note 1)
THERMAL DRIFT
0.04% per deg.C change in AVR ambient(note 2)
TYPICAL SYSTEM RESPONSE
AVR response20ms
Filed current to 90%80ms
Machine volts to 97%300ms
EXTERNAL VOLTAGE ADJUSTMENT
±10% with 1k ohm 1 watt trimmer (see note 3)
UDER FREQUENCY PROTECTION
Set point95% HZ(see note 4)
Slope170% down to 30HZ
UNIT POWER DISSIPATION
12 watts maximum
BUILD UP VOLTAGE
4 volts @ AVR terminals
ANALOGUE INPUT
Maximum input±5D dc( see note 5)
Snsitivity1V for 5% generator volts(adjustable)
Input resistance1J ohm
QUADRATURE DROOP INPUT
10ohms burden
Max sensitivity:0.07A for 5% droop OPF
Max input:0.33A
ENVIRONMENTAL
Vibration20-100HZ50mm.sec
100HZ2KHZ3.3g
Operatingtemperature-40 to +70C
Relative humidity 0-70C95%(see note 6)
Storage temperature-55 to +80C