AC input voltage range |
88~264VAC; 124~370VDC |
AC inrush current (max.) |
Cold start, 70A at 230VAC |
DC adjustment range |
12V: 12~14V (only for SDR-75/120), 24V: 24~28V, 48V: 48~55V |
Overload protection |
Normally works within 110%~150% rated output power for 3 seconds and then shut down output voltage with auto-recovery (re-power on to recover for SDR-75) |
Overload protection |
>150% rated power or short circuit, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds |
Over voltage protection Range |
14~17V for 12V model |
Over voltage protection Type |
Shut down o/p voltage, re-power on to recover |
Over temp. protection |
Recovers automatically after temperature goes down |
Withstand voltage |
I/P-O/P:3kVAC, I/P-FG:1.5kVAC, O/P-FG:0.5kVAC, O/P-DC OK:0.5kVAC |
Working temperature |
-25~+70°C (refer to output derating curve) |
Safety standards |
UL508, TUV EN60950-1, GL approved |
EMC standards |
EN55022 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), EN61204-3; SEMI, GL |
Connection |
I/P: 3 poles, O/P: 4 poles screw DIN terminal |
Dimension (WxHxD)(mm) |
40x125.2x113.5 |