Server Technology STV-3206C Sentry Rack PDU 0U 36x C13 6x C19 30A 208V L6-30P

This listing is for one Server Technology (Legrand)  Sentry Smart Cabinet Distribution Rack PDUSome of the units available are "master" and some are "slave"Please let us know what you prefer - send us a message after checking out or contact us with any questions prior to purchasingPlease contact us with any questionsThank youASLOC: R-G/F-NW~~~~~~~~~~~~~~~Manufacturer Specs:Smart PDU - 5.0kW, STV-3206CKey FeaturesNETWORK MONITORINGGain access to valuable data through connections including HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.TEMPERATURE/HUMIDITY MONITORINGPrimary and Link units each support two external 10' (3m) T/H probes. Receive SNMP-based alerts and email notifications.AUTO-FLIP CURRENT DISPLAYEasy-to-read LEDs display current per phase to help prevent overloads and simplify three-phase load balancing in high-density cabinets.PER-INLET POWER SENSINGMeets ANSI C12.1 for billing-grade accuracy of Current per phase. PIPS includes voltage, active power, apparent power, power factor, and energy.BRANCH CIRCUIT PROTECTIONThis PDU meets the UL and IEC 60950-1 requirement for branch circuit protection through use of UL489 rated magnetic-hydraulic circuit breakers or UL248 fuses.HIGH RETENTION LOCKING OUTLETSReceptacles have high retention and are compatible with P-Lock type power cords.HIGH TEMPERATURE RATINGThis product has been tested and approved for safe and reliable operation in 60 °C data center environments.POWER PIVOT™The 90 degree rotatable power cord allows for standardized deployment at any facility no matter where power must be routed.FLEXIBLE MOUNTINGIncludes standard button mounts along with provisions for custom mounting brackets (contact Server Technology for details).DescriptionThe Server Technology® Smart PDU provides local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® technology provides accurate measurement of current (billing-grade), voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The Smart “Primary” PDU can be connected to a Smart “Link” PDU to extend the network access to the redundant or secondary power feed.InputsInput Voltage (V):208Input Plug:NEMA L6-30PInput Current (A):30Input Current Rated (A):24Input Power Capacity (kW):5.0OutputsConnectorRating(36) x IEC 60320/C13North American Rating: ≤ 12A @208V L-L (15A Peak)(6) x IEC 60320/C19North American Rating: ≤ 16A @208V L-L (20A Peak)Branch Circuit ProtectionUL489 Compliant 2-pole, 20A trip circuit breakers, two (2) branch, rating: ≤ 16A, 5 kAIC Interrupt RatingPhysicalDimensions: 69.0in tall x 2.2in wide x 2.25in deep [1753mm x 56mm x 58mm]EnvironmentalOperating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevationStorage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevationQuiescent / Unloaded Power Draw: < 10W for all configurationsCommunications & Security10/100/1000 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU}Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTPCertificationsNorth American:Safety (TUVR certified, cTUVus mark)UL Std. 60950-1, 62368-1CAN/CSA-C22.2 No. 60950-1, CAN/CSA-C22.2 No. 62368-1EMCFCC Part 15 Subpart B Sections 15.107 & 15.109, Class ACAN ICES-003, Class AMeasurement AccuracyInput Measurement Accuracy:LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolutionGUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp)Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)Active Power = ± 1% at 1 watt resolutionApparent Power = ± 1% at 1 volt-amp resolutionPower Factor = ± 3% at 0.01 resolutionCrest Factor = ± 10% at 0.1 resolutionEnergy = ± 1% at 0.1 kilowatt-hour resolution
This listing is for one Server Technology (Legrand)  Sentry Smart Cabinet Distribution Rack PDU

Some of the units available are "master" and some are "slave"

Please let us know what you prefer - send us a message after checking out or contact us with any questions prior to purchasing

Please contact us with any questions

Thank you

AS
LOC: R-G/F-NW

~~~~~~~~~~~~~~~
Manufacturer Specs:

Smart PDU - 5.0kW, STV-3206C

Key Features

  • Network monitoring
    NETWORK MONITORING
    Gain access to valuable data through connections including HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.
  • Enviromental monitoring
    TEMPERATURE/HUMIDITY MONITORING
    Primary and Link units each support two external 10' (3m) T/H probes. Receive SNMP-based alerts and email notifications.
  • Input current monitor
    AUTO-FLIP CURRENT DISPLAY
    Easy-to-read LEDs display current per phase to help prevent overloads and simplify three-phase load balancing in high-density cabinets.
  • Pips
    PER-INLET POWER SENSING
    Meets ANSI C12.1 for billing-grade accuracy of Current per phase. PIPS includes voltage, active power, apparent power, power factor, and energy.
  • Branch circuit protection
    BRANCH CIRCUIT PROTECTION
    This PDU meets the UL and IEC 60950-1 requirement for branch circuit protection through use of UL489 rated magnetic-hydraulic circuit breakers or UL248 fuses.
  • High retention outlets
    HIGH RETENTION LOCKING OUTLETS
    Receptacles have high retention and are compatible with P-Lock type power cords.
  • High temp
    HIGH TEMPERATURE RATING
    This product has been tested and approved for safe and reliable operation in 60 °C data center environments.
  • Power pivot
    POWER PIVOT™
    The 90 degree rotatable power cord allows for standardized deployment at any facility no matter where power must be routed.
  • Flexible mounting
    FLEXIBLE MOUNTING
    Includes standard button mounts along with provisions for custom mounting brackets (contact Server Technology for details).

Description

The Server Technology® Smart PDU provides local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® technology provides accurate measurement of current (billing-grade), voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The Smart “Primary” PDU can be connected to a Smart “Link” PDU to extend the network access to the redundant or secondary power feed.

Inputs

Input Voltage (V):208
Input Plug:NEMA L6-30P
Input Current (A):30
Input Current Rated (A):24
Input Power Capacity (kW):5.0

Outputs

ConnectorRating
(36) x IEC 60320/C13North American Rating: ≤ 12A @208V L-L (15A Peak)
(6) x IEC 60320/C19North American Rating: ≤ 16A @208V L-L (20A Peak)

Branch Circuit Protection

UL489 Compliant 2-pole, 20A trip circuit breakers, two (2) branch, rating: ≤ 16A, 5 kAIC Interrupt Rating

Physical

Dimensions: 69.0in tall x 2.2in wide x 2.25in deep [1753mm x 56mm x 58mm]

Environmental

Operating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
Quiescent / Unloaded Power Draw: < 10W for all configurations

Communications & Security

10/100/1000 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)
Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) -
Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP

Certifications

North American:
Safety (TUVR certified, cTUVus mark)
  • UL Std. 60950-1, 62368-1
  • CAN/CSA-C22.2 No. 60950-1, CAN/CSA-C22.2 No. 62368-1
EMC
  • FCC Part 15 Subpart B Sections 15.107 & 15.109, Class A
  • CAN ICES-003, Class A

Measurement Accuracy

Input Measurement Accuracy:
LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp)
Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
Active Power = ± 1% at 1 watt resolution
Apparent Power = ± 1% at 1 volt-amp resolution
Power Factor = ± 3% at 0.01 resolution
Crest Factor = ± 10% at 0.1 resolution
Energy = ± 1% at 0.1 kilowatt-hour resolution