Range of produc | Compact NS100...630 |
---|---|
Product or component type | Circuit breaker |
Device short name | Compact NS400N |
circuit breaker name | Compact NS400N |
Device application | Distribution |
Poles description | 4P |
Protected poles description | 3t 4t 3t + N/2 |
Neutral position | Left |
Network type | AC DC |
Network frequency | 50/60 Hz |
[In] rated current | 400 A at 40 °C 320 A at 65 °C |
[Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 750 V DC conforming to IEC 60947-2 |
Breaking capacity code | N |
Breaking capacity | 85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
utilisation category | Category A |
Trip unit name | STR23SE |
Trip unit technology | Electronic |
Trip unit rating | 400 A |
Protection type | Overload protection (long time) Short time short-circuit protection Instantaneous short-circuit protection Protection of the fourth pole |
Pollution degree | 3 conforming to IEC 60947 |