![](https://www.automation.siemens.com/bilddb/interfaces/InterfaceImageDB.asmx/GetImageVariantByMLFB?interfaceuserid=TED&objecttype=4,70&imagevariantid=16,19,9&articlenumber=6ES71532BA020XB0&lang=en,XX) | ***SPARE PART*** SIMATIC DP, ET 200M INTERFACE IM 153-2 HIGH FEATURE FOR MAX. 12 S7-300 MODULES, WITH REDUNDANCY, TIME STAMPING FIT FOR ISOCHRONE MODE NEW FEATURES: UP TO 12 MODULES / STATION SLAVE INITIATIVE FOR DRIVE ES AND SWITCH ES EXTENDED DATA FOR HART SECONDARY VARIABLES OPERATON OF 64-CHANNEL MODULES 32 SIGNALS / SLOT |
General information |
Product type designation | IM 153-2 DP HF |
Vendor identification (VendorID) | 801Eh |
Supply voltage |
Rated value (DC) |
|
● 24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | 2,5 A |
Mains buffering |
● Mains/voltage failure stored energy time | 5 ms |
Input current |
Current consumption, max. | 600 mA |
Inrush current, typ. | 3 A |
I²t | 0.1 A²·s |
Output voltage |
Rated value (DC) | 5 V |
Output current |
for backplane bus (5 V DC), max. | 1.5 A |
Power loss |
Power loss, typ. | 5.5 W |
Address area |
Addressing volume |
● Inputs | 244 byte |
● Outputs | 244 byte |
Hardware configuration |
Number of modules per DP slave interface, max. | 12 |
Time stamping |
Accuracy | 1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules |
Number of message buffers | 15 |
Messages per message buffer | 20 |
Number of stampable digital inputs, max. | 128; Max. 128 signals/station; max. 32 signals/slot |
Time format | RFC 1119 |
Time resolution | 0.466 ns |
Time interval for transmitting the message buffer if a message is present | 1 000 ms |
Time stamp on signal change | rising / falling edge as signal entering or exiting |
Interfaces |
Transmission procedure | RS 485 |
Interface physics, RS 485 | Yes |
Interface physics, FOC | No |
PROFIBUS DP |
● Node addresses | 1 to 125 permitted |
● automatic detection of transmission rate | Yes |
● Output current, max. | 70 mA |
● Transmission rate, max. | 12 Mbit/s |
● SYNC capability | Yes |
● FREEZE capability | Yes |
● Direct data exchange (slave-to-slave communication) | Yes; Sender |
● Design of electrical connection of PROFIBUS interface | 9-pin sub D |
1. Interface |
DP slave |
● GSD file | SI04801.GSG |
● automatic baud rate search | Yes |
Protocols |
Bus protocol/transmission protocol | PROFIBUS DP to EN 50170 |
Potential separation |
Potential separation exists | Yes |
Isolation |
Isolation tested with | Isolation voltage 500 V |
Degree and class of protection |
IP degree of protection | IP20 |
Ambient conditions |
Ambient temperature during operation |
● min. | 0 °C |
● max. | 60 °C |
Air pressure acc. to IEC 60068-2-13 |
● Installation altitude above sea level, max. | 3 000 m |
Configuration |
Configuration software |
● STEP 7 | Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
Dimensions |
Width | 40 mm |
Height | 125 mm |
Depth | 117 mm |
Weights |
Weight, approx. | 360 g |
|