Bulletin 8888
Safeguard and Control Single Burner System
— Single burner flame supervision
—
Single or dual fuel
—
Choice of flame scanners:
UV, UV self-check, and flame rod
—
Optional high temperature limit
—
Optional 1400°F bypass
— Optional process temperature controller (with or without
ramp/soak)
—
Robust printed circuit
board assembly
—
UL listing available
—
Fused outputs
— Start-up mode toggle switches
(hold low fire for tuning)
—
Plug-in components
— Wiring for mini-fuel train
and valve proving system
— Wiring
for large selection of compatible actuators
SPECIFICATIONS
—
NEMA 4X enclosure, 16"
H ´ 14" W ´ 8" D, with window
to observe system
status
— Power requirements:120 V ac, 50 or 60 Hz, 8 A max.
—
Door mounted
equipment: run/stop pushbutton, auto start selector
— Flame relay: Honeywell RM7888A
—
Status
LED's: Power, pilot, flame on, main fuel powered, and alarm
— Board mounted switches:
Power Fuel select
Motor low or force modulation* Pilot only or main valve select*
—
Board mounted status LED's: Main power on Common limits
Fuel 1 limits
Fuel 2 limits Limits complete Purging
Low fire
Main
fuel open
— Provision for limit terminations:
Five common
limits
Three fuel 1 limits Three fuel 2 limits High temperature limit
* Used for start-up
lletin 8888
Page 2
— Terminations: 66 terminals in 2 staggered rows to simplify connections, accept up to AWG 12 wire
—
Dry contact
outputs, form C for limits complete, fuel off, and lock out alarm. Contact
rating 120 V ac, 2 A
—
Options (panel rated NEMA 12 with controllers mounted)
High temperature limit
controller
Process temperature controller (4 to 20mA or 120 V output)
Ramp/soak controller
available UL classification of panel (UL508)
UV,
self-check UV, or flame rod sensors
— Cabinets available:
Fiberglass Painted metal Stainless steel
—Spare parts, replaceable plug-in components: Relay (LCR, ACR)
Relay
(FOCR, FSCR)
Timer (PTR)
Flame relay
Fuse, 10 A, slow blow
Fuse, 3 A, fast blow
The RM7888A Flame Relay has
been a successful joint development project between North American, a primary leader in combustion solutions, and Honeywell, a global leader in electronic technology. This synergistic effort has led to product features that include Flame Scanner choices,
direct spark or pilot ignition offering relight capabilities, control motor operation,
and PLC interconnection--all in one simple to operate
unit.
Other features include an adjustable purge timer, plug and play components, and fused outputs.
Its NEMA 4X enclosure with a transparent window assists in
monitoring burner status LED's and the optional keyboard
display module.