200W Single Output Switching Power Supply L R S - 2 0 0 s e r i e s
MODEL |
LRS-200-3.3 |
LRS-200-4.2 |
LRS-200-5 |
LRS-200-12 |
LRS-200-15 |
LRS-200-24 |
LRS-200-36 |
LRS-200-48 |
|
OUTPUT |
DC VOLTAGE |
3.3V |
4.2V |
5V |
12V |
15V |
24V |
36V |
48V |
RATED CURRENT |
40A |
40A |
40A |
17A |
14A |
8.8A |
5.9A |
4.4A |
|
CURRENT RANGE |
0 ~ 40A |
0 ~ 40A |
0 ~ 40A |
0 ~ 17A |
0 ~ 14A |
0 ~ 8.8A |
0 ~ 5.9A |
0 ~ 4.4A |
|
RATED POWER |
132W |
168W |
200W |
204W |
210W |
211.2W |
212.4W |
211.2W |
|
RIPPLE & NOISE (max.) Note.2 |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
150mVp-p |
200mVp-p |
200mVp-p |
|
VOLTAGE ADJ. RANGE |
2.97 ~ 3.6V |
3.6 ~ 4.4V |
4.5 ~ 5.5V |
10.2 ~ 13.8V |
13.5 ~ 18V |
21.6 ~ 28.8V |
32.4 ~ 39.6V |
43.2 ~ 52.8V |
|
VOLTAGE TOLERANCE Note.3 |
±3.0% |
±4.0% |
±3.0% |
±1.5% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
|
LINE REGULATION Note.4 |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
LOAD REGULATION Note.5 |
±2.5% |
±2.5% |
±2.0% |
±1.0% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
|
SETUP, RISE TIME |
1300ms, 50ms/230VAC 1300ms,50ms/115VAC at full load |
||||||||
HOLD UP TIME (Typ.) |
16ms/230VAC 12ms/115VAC at full load |
||||||||
INPUT |
VOLTAGE RANGE |
90 ~ 132VAC / 180 ~ 264VAC by switch 240 ~ 370VDC (switch on 230VAC) |
|||||||
FREQUENCY RANGE |
47 ~ 63Hz |
||||||||
EFFICIENCY (Typ.) |
83% |
86% |
87% |
87.5% |
88% |
89.5% |
89.5% |
90% |
|
AC CURRENT (Typ.) |
4A/115VAC 2.2A/230VAC |
||||||||
INRUSH CURRENT (Typ.) |
COLD STAR 60A/115VAC 60A/230VAC |
||||||||
LEAKAGE CURRENT |
<2mA / 240VAC |
||||||||
PROTECTION |
OVER LOAD |
110 ~ 140% rated output power |
|||||||
3.3~36V Hiccup mode, recovers automatically after fault condition is removed. 48V Shut down and latch off o/p voltage, re-power on to recover. |
|||||||||
OVER VOLTAGE |
3.8 ~ 4.45V |
4.6 ~ 5.4V |
5.75 ~ 6.75V |
13.8 ~ 16.2V |
18 ~ 21V |
28.8 ~ 33.6V |
41.4 ~ 46.8V |
55.2 ~ 64.8V |
|
3.3~36V Hiccup mode, recovers automatically after fault condition is removed. 48V Shut down and latch off o/p voltage, re-power on to recover. |
|||||||||
OVER TEMPERATURE |
3.3~36V Hiccup mode, recovers automatically after fault condition is removed. 48V Shut down and latch off o/p voltage, re-power on to recover. |
||||||||
ENVIRONMENT |
WORKING TEMP. |
-25 ~ +70℃ (Refer to "Derating Curve") |
|||||||
WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
||||||||
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
||||||||
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃) |
||||||||
VIBRATION |
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes |
||||||||
SAFETY |
SAFETY STANDARDS |
IEC/UL 62368-1, BSMI CNS14336-1, BS EN/EN60335-1,EAC TP TC 004, KC K60950-1(for LRS-200-12/24 only), BIS IS13252(Part1): 2010/IEC 60950-1: 2005, AS/NZS62368.1 approved; Design refer to BS EN/EN62368-1 |
|||||||
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
||||||||
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH |
||||||||
EMC EMISSION |
Compliance to BSMI CNS13438, EAC TP TC 020,KC KN32,KN35(for LRS-200-12/24 only) |
||||||||
EMC IMMUNITY |
Compliance to EAC TP TC 020,KC KN32,KN35(for LRS-200-12/24 only) |
||||||||
OTHERS |
MTBF |
347.5K hrs min. MIL-HDBK-217F (25℃) |
|||||||
DIMENSION |
215*115*30mm (L*W*H) |
||||||||
PACKING |
0.66Kg; 15pcs/10.9Kg/0.78CUFT |