PENN. P/N: P70SA-1C. MICRO-SET CONVERTIBLE DUAL PRESSURE CONTROL., SPDT., HIGH PRESSURE FIELD CONVERTIBLE RESET., MANUAL RESET., LOW SIDE RANGE: 12" HG VACUUM TO 80 PSIG., HIGH SIDE RANGE: 100 PSIG TO 500 PSIG., DIFFERENTIAL: 5 TO 35 PSI., (2) SPDT, INDEPENDENT HI/LO SWITCH., 36" LONG COPPER CAPILLARY TUBE WITH 1/4" BRASS FLARE NUTS., 7/8" DIAMETER KNOCKOUT HOLE FOR CONDUIT CONNECTION., 120 VAC TO 600 VAC., NEMA 1., ELECTROMECHANICAL PRESSURE CONTROL., OVERALL DIMMENSIONS: 5 5/8" LONG X 4 1/2" HIGH X 2" THICK., BLACK & SILVER COLORED., INCLUDES: ONE DUAL PRESSURE CONTROL, MOUNTING BRACKET, TWO MOUNTING SCREWS, INSTALLATION INSTRUCTIONS, PACKAGING AND BOX., ORIGINAL GENUINE OEM REPLACEMENT PART., GUARANTEED TO WORK PERFECTLY., BRAND NEW CONDITION., NEVER USED., I CAN SUPPLY MORE PICTURES IF REQUESTED.


Description:


Johnson Controls (Penn) 36" Capillary with 1/4" Flare Nut, 120 to 600 VAC, 5 to 35 PSI Low Side, 65 PSI Fixed/Manual Reset Lockout High Side Differential, NEMA 1, (2) SPDT, Electromechanical Pressure Control


Features & Benefits:




Specifications:














Description:


P70 single and dual function pressure controls are used in commercial air conditioning and refrigeration applications. The load-carrying contacts provide direct control of A.C. motors within the control?s rating. (See cover label for the electrical rating.)


The controls can be used with R- 12, R-22, R-500, or R-502 refrigerants. Specific models for ammonia applications are also available. The MICRO-SET construction of low pressure controls and low side of dual models permits differentials to a minimum of 5 psi (34 kPa).


Specifications: