500 Foot Spool
Specification Sheet

Lake Cable Part #: P183CS

Description: 18 AWG 3 conductor 7 strand bare copper wire with plenum rated PVC insulation, shielded, with
an overall plenum rated PVC jacket

1. Conductor
    1.1. AWG Size & Stranding: 18 AWG 7 Strands Class B
    1.2. Material: Annealed Bare Copper
    1.3. Conductor Count: 3 Conductors
2. Insulation
    2.1. Material: Plenum Rated Polyvinylchloride
    2.2. Wall Thickness: 0.007”
    2.3. Diameter: 0.059” ± 0.002”
    2.4. Color Code: Black, Red, White
3. Assembly
   3.1. Nominal Lay Length: 3.00” LHL (4.00 Tw/Ft), Nominal
   3.2. Shield: Aluminum/Mylar Tape – 100% Coverage
   3.3. Drain Wire: 24 AWG 7 Strand Tinned Copper
4. Jacket
   4.1. Material: Tube Extruded Plenum Rated PVC
   4.2. Wall Thickness: 0.015”
   4.3. Diameter: 0.159” ± 0.015”
   4.4. Color: Natural
   4.5. Ripcord: Yes
   4.6. Weight: 25 Lbs/Mft
5. Markings
   5.1. Type: Cable permanently identified via surface inkjet print
   5.2. Legend: LAKE CABLE E171202 18AWG 3C SHIELDED 75C (UL) CL3P OR FPLP OR C(UL)US
   CMP FT6 "ROHS COMPLIANT" MADE IN USA
   5.3. Footage Markers: Yes (Ascending/Descending)
6. Nominal Electricals
   6.1. Impedance: 37 Ω ± 10%
   6.2. Capacitance: 50 pF/ft. ± 10%
   6.3. DC Resistance: 6.60 Ω/Mft. @ 20°C
7. Standards
   7.1. Cable suitable for installation under NEC (NFPA 70) articles 800, 725 and 760 guidelines
   7.2. Cable suitable for installation in Canada under Section 60 of CEC, Part I
   7.3. C(UL)US listed as CMP per UL standard 444 and per CSA C22.2 No. 214-17
   7.4. UL listed as CL3P per UL standard 13 or FPLP per UL standard 1424
   7.5. Cable meets NFPA 262 (Steiner tunnel) flame test
   7.6. Cable meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
   7.7. Cable is REACH compliant per Regulation (EC) No 1907/2006 (235) Updated June 14, 2023
   7.8. Made in the USA
   7.9. WARNING: This product may contain chemicals, such as Vinyl Chloride, known to the state of

California to cause cancer. For more information, go to www.P65Warnings.ca.gov. Wash hands after
handling

ALL SPECIFIED PARAMETERS WITHOUT A TOLERANCE ARE NOMINAL AND SUBJECT TO VERIFICATION. LAKE
CABLE IS NOT RESPONSIBLE FOR UNKNOWN PERFORMANCE ATTRIBUTES THAT WERE NOT MADE KNOWN
TO LAKE CABLE AT THE TIME OF DESIGN.