Generator Set Controller DC62D for Diesel/Gas Genset Parameters Monitoring

This series of controllers is specially designed for starting, stopping, parameter monitoring and fault monitoring of diesel, gasoline and gas generator sets and has the function of parameter setting.

The controller adopts a 4.3-inch TFT color large-screen LCD to display the relevant parameters of the generator set, a new and original UI design, and the parameters are displayed by analog pointers and numbers. The LCD screen can display a variety of current fault states at the same time, and can effectively implement protection and stop when the generator set is not working normally.

The controller built-in simplified Chinese, English and other display interfaces can be selected, and any language interface can be customized according to customer requirements. All parameters of the controller can be adjusted through the buttons on the controller panel, or adjusted and monitored through the USB port or RS485 interface using a PC, which can be widely used in various types of generator set automation systems.

 

Main Features:

 

Parameters Display:

Engine RPM

Engine oil pressure

Engine water temperature

Engine fuel temperature

Engine cylinder temperature

Engine Tank temperature

Engine fuel level

Engine battery voltage

Charging voltage

Mains Frequency (only for DC62D)

Mains phase voltage L-N(only for DC62D)

Mains phase voltage L-L(only for DC62D)

Generator 3 Phase voltage L-N

Generator 3 Phase voltage L-L

Generator 3 phase current A

Generator Frequency Hz

Generator Power Factor COSφ

Generator active power KW

Generator apparent power KVA

Generator reactive power KVar

Current loading rate %

Total average loading rate %

Current consumption KWH

Total consumption Kwh

Total Crank times

Current running time

Total running time

 

Protection:

Over speed

Under speed

Low oil pressure

High water temperature

High Oil temperature

High Cylinder Temperature

High Tank temperature

Low fuel level

Low oil level

External emergency alarm

D+ Opened

RPM Lost

Sensor Open

Over Frequency

Under Frequency

Over voltage

under voltage

over current

Non-balance of current

Over power

Lack of Phase

reverse phase sequence

Gen load failure

Gen unload failure

Mains Load failure

Mains unload failure

Primary maintenance expire

Secondary maintenance expire

Maintenance expire

Low water level alarm

Emergency Stop

Crank failure

Over battery voltage

Under Battery voltage

Charging failure

Battery Charging failure

Stop Failure

 

Parameters:

Options

Parameters

Working voltage

DC8V----36V Continuous

Power consumption

Standby24VMAX 1W

Working24VMAX 5W

AC Voltage Input

1P2W 30VAC-276VAC(ph-N)

2P3W 30VAC-276VAC(ph-N)

3P4W 30VAC-276VAC(ph-N)

Rotate speed sensor Frequency

200-10000Hz

MAX Accumulating Time

99999.9HoursMin Store time:6min

Fuel Relay Output

16Amp DC+VE Supply voltage

Start Relay Output

16Amp DC+VE Supply voltage

Programmable Relay output 1

5Amp DC+VE Supply voltage

Programmable Relay output 2

5AMP Non-contact-Normal open--Normal close output

Programmable Relay output 3

5AMP Non-contact Normal Open output

Programmable Relay output 4

5AMP Non-contact normal open output

Excitation output

Max 1AMP DC+VE supply voltage

Switch value input

Available if connecting with Battery -

Working condition

-20-65℃

Storage condition

-40-85℃

Protection Level

IP54when waterproof rubber gasket is added between controller and its panel

Overall dimension

210mm*160mm*50mm

Panel cutout

186mm*142mm

Weight

0.85Kg

 

Package include:

1 x DC62D Genset Controller