The FireLite MS-2 and MS-2E Fire Alarm Control Panels (FACPs) bring the latest in microprocessor technology to conventional fire controls. The MS-2 is compatible with the i3™ smoke detectors from System Sensor with drift compensation, maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices with three selections for manufacturer protocol. The Notification Appliance Circuit (NAC) protocol can silence audible devices while strobes continue to flash, using a single pair of wires.
The MS-2 is compatible with conventional input devices such as two- and four-wire smoke detectors; pull stations, waterflow devices, tamper switches and other normally open contact devices. Refer to the Fire•Lite Device
Features:
- Two Style B (Class B) Initiating Device Circuits (IDCs).
- One Style Y (Class B) NAC.
- 24 VDC.
i3™ Technology features:
- Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused by dust accumulation.
- Maintenance Alert LEDs (per zone) warn of excessive dirt accumulation, preventing false alarms (meets NFPA 72 requirements).
- Detector sensitivity is automatically measured by the detector, which automatically adjusts its sensitivity back to the factory settings when it becomes more sensitive due to contaminants settling in the chamber.
- Wireless handheld sensitivity meter eliminates the need for voltmeters, magnets, and a physical connection to the detector. The reader displays sensitivity in terms of percent per foot obscuration and provides text status indication.
- Supervisory LED (per zone) provides warning if a detector senses temperature approaching freezing.
- Special test protocol and LED indication allows quick test of all detectors without need for a ladder.
NAC synchronization features:
- Synchronization of standard ANSI audible signals as required by NFPA 72.
- Synchronization of ADA compliant strobes per NFPA 72.
- Selectable for System Sensor, Wheelock, and Gentex protocols.
- Selective Silence for manual silence of horns while strobes continue to flash on the same NAC.
- Alarm verification selectable for each zone.
- Disable switches provided per zone.
NAC programmable for:
- Silence Inhibit
- Auto Silence
- Strobe Synchronization
- Selective Silence (horn-strobe mute)
- Temporal or Steady signal
- Silenceable or Nonsilenceable
- Silent or audible Walk Test operation mode commanded from the front keypad, with automatic return-to-normal after one hour of inactivity.
- Each zone may be programmed for supervisory or fire; each zone has separate red and yellow LEDs.
- Disable switches provided for each zone.
- Form-C Alarm and Trouble relays.
- 3.0 amps total usable current.
- Piezo sounder for alarm, trouble, supervisory and maintenance.
Control buttons:
- ACK (Acknowledge)
- Alarm Silence
- Reset
- Walk Test
- Zone Enable/Disable (one per zone)
LED indicators:
- Fire Alarm (one per zone)
- Supervisory (one per zone)
- Trouble (one per zone)
- Maintenance (one per zone)
- AC Power
- NAC Disable
- Zone Disable
- NAC Fault
- System Trouble
Specifications
AC POWER — TB8
- MS-2: 120 VAC, 50/60 Hz, 2.3 A.
- MS-2E: 240 VAC, 50 Hz, 1.15 A.
- Wire Size: Minimum 14 AWG (2.0 mm) with 600 V insulation.
Battery (Sealed Lead-Acid Only) — J8
- Maximum charging circuit: normal flat charge 27.6 VCD @ 0.8 A.
- Maximum battery charger capacity: 18.0 AH battery (two 7.0 AH batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the Fire•Lite BB-17F).
Initiating Device Circuit — TB3
- Alarm zones 1 & 2.
- Power-limited circuitry.
- Operation: all zones Style B (Class B).
- Normal operating voltage: nominal 20 VDC.
- Alarm current: 15 mA minimum.
- Short-circuit current: 40 mA maximum.
- Maximum loop resistance: 100 ohms.
- End-of-line resistor: 4.7K ohm, watt (P/N 71252).
- Standby current: 4 mA.
- Compatible devices: refer to the FireLite Device Compatibility
- Document no. 15384 for a complete list of compatible devices
NOTIFICATION APPLIANCE CIRCUIT — TB2
- One NAC.
- Power-limited circuitry.
- Normal operating voltage: nominal 24 VDC.
- Maximum signalling current: 2.5 A total with standard transformer.
- End-of-line resistor: 4.7K ohm, watt (P/N 71252).
- Compatible devices: refer to the Fire•Lite Device Compatibility
- Document no. 15384 for a complete list of compatible devices
Form C-Relays
- Trouble Relay TB5 (fail-safe).
- Alarm Relay TB6.
- Relay contact ratings: 2.0 A @ 30 VAC (resistive).
Auxiliary Output Resettable Power — TB1
- Operating voltage: nominal 24 VDC.
- Maximum available current: 500 ma — appropriate for powering
- Four-wire smoke detectors
- Power-limited circuitry.
Cabinet Dimensions
- Door: 15.342" (38.97 cm) high x 14.667" (37.28 cm) wide x 0.375" (0.95 cm) deep.
- Backbox: 15.0" (38.10 cm) high x 14.5" (36.83 cm) wide x 3.0" (7.62 cm) deep.
Backbox Mounting
- The cabinet can be surface mounted. The door is removable
- during installation by opening and lifting it off the hinges. The
- cabinet mounts using two key slots at the top of the backbox and
- two additional 0.25" diameter holes at the bottom.
Listings and Approvals
- UL Listed: S624.
- MEA: 297-01-E.
- CSFM: 7165-0075:200.