mcb DZ47-60 1P C25
CHINT rated current of 60A and below, to act overload, short-circuit protection.
DZ47-60 miniature circuit breaker, only available for sales in Commonwealth of Independent States, is mainly used in the circuit of AC 50Hz/60Hz, rated voltage of 400V and below, rated current of 60A and below, to act overload, short-circuit protection. It can also turn on or off the electrical appliance and lighting circuit infrequently under normal conditions, but not applicable for direct protection of high sensibility and high capacitive load of motor and electric equipment, capacitor cabinets, etc.
Standard: IEC 60898-1.
mcb Normal working conditions:
environmental temperature: 5 C ~ + 40 C; The average no more than 35 C within 24 h.
Height: installation location altitude does not exceed 2000 m.
mcb the main parameters and technical performance:
according to the rated current In points: 1A, 2A, 3A, 4A, 5A, 6A, 10A, 15A, 16A, 20A, 32A, 40A, 50A, 60A.
the number:
A. unipolar;
B. diode;
C. three pole;
D. quadrupole.
according to instantaneous tripping circuit breaker type points:
A.C type (5 ~ 10 in);
B.D type (10 ~ 16 in);
mechanical and electrical life:
Home Garyical life: not less than 4000 times;
Mechanical life: not less than 10000 times.
mcb DZ47-60(C) Type
Rated current(A) | number | Voltage (V) | On-off capacity (A) |
C1-C40 | 1 | 230/400 | 6000 |
C1-C40 | 2,3,4 | 400 | 6000 |
C50-C60 | 1 | 230/400 | 4000 |
C50-C60 | 2,3,4 | 400 | 4000 |
mcb DZ47-60(D) Type
Rated current(A) | number | Voltage (V) | On-off capacity (A) |
D1-D60 | 1 | 230/400 | 4000 |
D1-D60 | 2,3,4 | 400 | 4000 |
Connection: for 25 mm below the wire connection, 2.0 N · m torque.
Rated current(A) | Copper wires nominal cross-sectional area (mm) |
1-6 | 1 |
10 | 1.5 |
16,20 | 2.5 |
25 | 4 |
32 | 6 |
40,50 | 10 |
60 | 16 |