Connectors |
||
|
RELAY OUTPUT 1 – 8 |
(1) 16-pin 5mm detachable terminal block
comprising (8) normally open, isolated relays; |
|
DIGITAL IN 1 – 4 |
(1) 5-pin 5mm detachable terminal block
comprising (4) digital or analog input ports (referenced to GND); |
|
NET |
(2) 6-pin RJ11 female, Cresnet slave ports,
paralleled; |
|
12VDC |
(1) 2.5mm barrel DC power jack; |
Indicators |
||
|
PWR |
(1) green LED, indicates power supplied from
Cresnet network or local power pack |
|
NET |
(1) amber LED, indicates communication with
Cresnet system |
|
INPUT 1 – 4 |
(4) red LEDs, indicate a high signal at each
corresponding digital input port |
|
RELAY 1 – 8 |
(4) red LEDs, indicate a closure at each
corresponding relay output port |
Power
Requirements |
||
|
Power Pack |
0.5 Amp @ 12 Volts DC; |
|
Cresnet Power Usage |
6 Watts (0.25 Amp @ 24 Volts DC) with no
power pack connected |
Environmental |
||
|
Temperature |
41° to 113°F (5° to 45°C) |
|
Humidity |
10% to 90% RH (non-condensing) |
Enclosure |
||
|
Chassis |
Metal, black finish |
|
Faceplate |
Extruded aluminum, black finish with
polycarbonate label overlay |
|
Mounting |
Freestanding or 1U 1/2-width 19-inch
rack-mountable (adhesive feet included, ST-RMK rack kit sold separately) |
Dimensions |
||
|
Height |
1.80 in (46 mm); |
|
Width |
7.07 in (180 mm) |
|
Depth |
6.32 in (161 mm) |
Weight |
||
|
1.96 lb (0.89 kg) |
|
INTERNATIONAL VERSION (230 VAC) |
||
|
STI-IO |
|
|
All the features and specifications of the
ST-IO except: |
|
|
Power
Requirements |
|
|
Power Pack |
0.5 Amp @ 12 Volts DC; |
|
Cresnet Power Usage |
6 Watts (0.25 Amp @ 24 Volts DC) with no