We are REKUPEX and we offer the high efficiency recuperative exchangers for your heat recovery ventilation systems and air recuperative project. We are happy to be official proud dealer of Czech producer RECUTECH.
If you have any questions, don´t hesitate to contact us.
Price in this listing includes over 19% selling & transaction fees that we need to pay to Ebay. Check more pictures: rekupex cz
ABOUT RSF+ plastic air to air exchangers
The RSF+16 plastic heat exchanger
offers the highest effi ciency and optimum
pressure drop thanks to the unique plate
shape and 3,2 mm plate distance. The product
is available in lengths from 100 mm to 600 mm.
The Net Energy Performance is the
difference between the energy recovered
by the heat exchanger and energy
necessary to overcome its pressure drop by
the fans. The RSF+16 and generally
RECUTECH heat exchangers achieve top
values of this important parameter.
Every single product manufactured in
RECUTECH including the RSF+16
goes through strict tightness control.
We guarantee that the leakage of our
heat exchangers is always below 0,5 % of the
nominal air fl ow.
RECUTECH are committed to making the best
efforts to protect the environment. All our products are strictly silicone free.
The RSF+16 is ideal solution for compact
residential heat recovery units. The ratio of
effi ciency and pressure drop provides you with
the best Net Energy Performance. The
dimensions are compatible with the most
common solution on the market (366x366).
Efficiency up to 95 %
Lamellas welded with ultrasound
Manufactured from HPS without silicone
Protects the environment as well as improves SFP
Lowered pressure drop compared to the similar products on the market
Using the mobile app? Copy this link into your browser:
Results of exchanger testing:
Tested according to EN 308. The manufacturer provides design software for precise calculation of any intake conditions
The inward/outward air flow ratio is 1:1, the outward air temperature -5 °C, and relative humidity 25%. Internal air temperature 25 °C, relative humidity 80%.
Air flow volume 50 m3/h - Efficiency 95,1% - Face air flow speed upon entering the recuperator 0,5 m/s - Pressure drop - supply - 26,2 Pa, exhaust - 41,2 Pa
Air flow volume 120 m3/h - Efficiency 93,6% - Face air flow speed upon entering the recuperator 1,5 m/s - Pressure drop - supply - 139,4 Pa, exhaust - 222,1 Pa
Air flow volume 170 m3/h - Efficiency 93% - Face air flow speed upon entering the recuperator 2,1 m/s - Pressure drop - supply - 240 Pa, exhaust - 385,1 Pa
Diagram of Pressure drop PD [Pa] and Airflow volume AV [m3/h] - exchanger RSF+16-100-H-F-29
Input values for average winter season in the Czech Republic
The inward/outward air flow ratio is 1:1, the outward air temperature 1 °C, and relative humidity 78%. Internal air temperature 25 °C, relative humidity 28%, calculated by EUROVENT certificated software
Diagram of Efficiency EFF [%] and Airflow volume AV [m3/h] - exchanger RSF+16-100-H-F-29
Input values for average winter season in the Czech Republic
The inward/outward air flow ratio is 1:1, the outward air temperature 1 °C, and relative humidity 78%. Internal air temperature 25 °C, relative humidity 28%, calculated by EUROVENT certificated software
RECUBOX REKUPEX - protiproudý tepelný vým?ník vzduch-vzduch v oplá?t?ní
Video will open in a new window
Using the mobile app? Copy this link into your browser:
DIMENSIONS OF RSF+ EXCHANGERS
KEY TO CODING OF RSF+ EXCHANGERS
COMPUTER OPTIMIZED LAMELLA GEOMETRY AND EFFICIENCY
USE
The heat exchanger is used in heat recovery units, where it returns the exiting heat. The accumulated heat returns and thus significantly affects energy consumption. The efficiency of the heat exchanger is proportional to the outside temperature.
DESCRIPTION
The countercurrent air-to-air heat exchanger is made of durable materials. The casing is made of sheet aluminium and sealed with hot glue. The faces are glued using MS polymer. The heat exchangers do not contain silicone and they comply with the REACH 1907/2006 and RoHS 2011/65/EU Directives. It is composed of individual HIPS plastic plates, which are joined together by ultrasonic welding and are coated with sheet aluminium. The outgoing and incoming air flows between the plates and transfers energy to each other.
The outgoing and incoming air does not mix in the heat exchanger. Only the heat is transferred.
TECHNICAL DATA AND OPERATING CONDITIONS
Operating temperatures -20°C to +60°C.
Relative humidity 0% to 100%. Maximum recommended flow through the faces is 3 m/s on the inlet. We recommend using a heat exchanger with a balanced ratio between the outlet and inlet, or with a maximum imbalance of +/- 50%. The maximum pressuredifference between the inlet and the outlet is 800 Pa. The use of ultrasonic welding technology on all sizes ensures maximum tightness. The Eurovent certification guarantees up to 95% efficiency.
This exchanger you can install instead of Recair, Heatex, Holmak, Klingenburg or Eri recovery corporation
GERMAN DESCRIPTION
Die RSf+ Reihe ist die perfekte neue Lösung für ErP VU 1253/2014 Ecodesign Anforderungen. Die Reihe bietet verschiedene Optionen, damit Ihr Wohnungslüftungsgerät in die erste Klasse gehört. Die Kombination von Druckabfall und Effizienz sorgt für die richtigen Parameter für die Berechnung des spezifischen Energieverbrauchs
SPANISH DESCRIPTION
La serie RSF+ aporta una solución perfectamente nueva que cumple los requisitos ErP 2018. Esta serie permite elegir los parámetros óptimos haciendo hincapié en la pérdida de carga o la efectividad.