Applications

Combined supply and exhaust ventilation systems for various premises where high air capacity at relatively low system resistance is required. 
SFP fans can be used for the direct air exhaust or pressurization in smoke ventilation systems.
Productive capacity - Pressure - Sound level (3m)
SFP200  -  890m3/h - 110Pa - 50dB
SFP250 - 1100m3/h - 110Pa - 60dB
SFP300 - 2300m3/h - 110Pa - 61dB
SFP350 - 2600m3/h - 110Pa - 62dB
SFP400 - 3830m3/h - 110Pa - 63dB
SFP450 - 4800m3/h - 110Pa - 64dB
 
Input curren (A)
SFP200 - 0.25
SFP250 - 0.36
SFP300 - 0.66
SFP350 - 0.61
SFP400 - 0.82
SFP450 - 1.14
 
Power consumption (W)
SFP200 - 55
SFP250 - 80
SFP300 - 145
SFP350 - 135
SFP400 - 180
SFP450 - 250
 
Protection class (IP)
X4
 
Weight (kg)
SFP200 - 3.9
SFP250 - 5.8
SFP300 - 6.5
SFP350 - 8.5
SFP400 - 9.5
SFP450- 11.0

Speed control

Smooth speed control is performed by means of the verible speed controller. Several fans can be connected to one controller if the total power and operating current do not exceed the rated controller values (Control total Amps = 1.8)

Mounting

Fan is installed on the wall surface by means of a square mounting plate. 
The fan is powered through the external remote terminal box.
Power supply and installation shall be performed in compliance with the manual and wiring diagram on the terminal box.