Manufacturer: Tripp Lite
Model: Tripp Lite SmartPro UPS 1500VA 1350W, RM, 2U, 15A, 120V
Condition: New batteries, refurbished UPS
Part Number: SMART1500RM2U
Maximum output: 1350W / 1500VA
Typical backup time at half load: 13 minutes (675 Watts)
Typical backup time at full load: 4.5 minutes (1350 Watts)
Included: SMART1500RM2U UPS, no other accessories included
Warranty: 1 year full replacement warranty
Tripp Lite SmartPro 1500VA 1350W RM 120V SMART1500RM2U Manual
SMART1500RM2U - Tripp Lite SmartPro 1500VA Specifications:
Input:
Rated input current (Maximum Load) |
12A |
||
Nominal Input Voltage(s) Supported |
120V AC |
||
UPS Input Connection Type |
|
||
Input Circuit Breakers |
15A |
||
UPS Input Cord Length (ft.) |
10 |
||
UPS Input Cord Length (m) |
3.1 |
||
Recommended Electrical Service |
15A 120V |
||
Input Phase |
Single-Phase |
Output:
Output Volt Amp Capacity (VA) |
1500 |
||
Output kVA Capacity (kVA) |
1.5 |
||
Output Watt Capacity (Watts) |
1350 |
||
Output kW Capacity (kW) |
1.35 |
||
Power Factor |
0.9 |
||
Nominal Voltage Details |
120v nominal output in battery mode |
||
Frequency Compatibility |
60 Hz |
||
Output Voltage Regulation (Line Mode) |
-21%, +8% |
||
Output Voltage Regulation (Battery Mode) |
+/- 5% |
||
Load Management Receptacles |
Two switchable two-outlet 5-15R load banks |
||
Output AC Waveform (AC Mode) |
Sine wave |
||
Output AC Waveform (Battery Mode) |
Pure Sine wave |
||
Nominal Output Voltage(s) Supported |
110V; 115V; 120V |
||
Output Receptacles |
|
||
Individually Controllable Load Banks |
Yes |
Battery:
Full Load Runtime (min.) |
4.5 min. (1350w) |
Half Load Runtime (min.) |
13 min. (675w) |
DC System Voltage (VDC) |
36 |
Battery Recharge Rate (Included Batteries) |
Less than 4.5 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC93-2U |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
No |
Voltage Regulation:
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147 |
Overvoltage Correction |
Input voltages between 128 and 147 are reduced by 12% |
Undervoltage Correction |
Input voltages between 83 and 107 are boosted by 14% |
User Interface, Alerts & Controls:
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, |
Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown |
Surge / Noise Suppression:
UPS AC Suppression Joule Rating |
570 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
Physical:
Cooling Method |
Fan
|
Included Mounting Accessory Description |
Rail kit not included. There are several options available, a 4 post and a 2 post rail kit, details below |
Installation Form Factors Supported with Included Accessories |
4 post 19 inch rackmount
|
Installation Form Factors Supported with Optional Accessories |
Rail kit not included - Optional: 2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2- 9USTAND ); Wallmount ( 2POSTRMKITWM )
|
Minimum Required Rack Depth (cm) |
41.91
|
Minimum Required Rack Depth (inches) |
16.5
|
Optional Mounting Accessory Notes |
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
|
Primary Form Factor |
Rackmount
|
Primary UPS Depth (mm) |
342
|
Primary UPS Height (mm) |
88 |
Primary UPS Width (mm) |
439 |
Rack Height |
2U |
Shipping Dimensions (hwd / cm) |
22.10 x 50.80 x 59.69 |
Shipping Dimensions (hwd / in.) |
8.70 x 20.00 x 23.50 |
Shipping Weight (kg) |
26.54 |
Shipping Weight (lbs.) |
58.50 |
UPS Housing Material |
Steel |
UPS Power Module Dimensions ( |
8.76 x 43.94 x 34.16 |
UPS Power Module Dimensions (hwd, in.) |
3.45 x 17.3 x 13.45 |
UPS Power Module Weight (kg) |
21.09 |
UPS Power Module Weight (lbs.) |
46.5 |
Environmental:
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
267 |
Battery Mode BTU / Hr. (Full Load) |
1012 |
AC Mode Efficiency Rating (100% Load) |
95% |
Audible Noise |
45 dBA maximum, front side 1m |
Communications:
Network Management Cards |
|
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports , download PowerAlert Local software at http://www.tripplite.com/poweralert |
Communications Cable |
USB and DB9 cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
Network UPS Tools Compatibility |
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at |
Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |