product range | TeSys GV3 |
---|---|
range | TeSys Deca TeSys Deca |
device short name | GV3P |
product name | TeSys GV3 TeSys Deca |
product or component type | motor circuit breaker |
device application | Engine protection |
trip unit technology | Thermal-magnetic |
poles description | 3P |
---|---|
network type | A.C. |
utilization category | AC-3 conforming to IEC 60947-4-1 |
network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
fixing mode | 35mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) |
operating position | Any position |
motor power kW | 18.5 kW at 400/415 V AC 50/60 Hz 22 kW at 500 V AC 50/60 Hz 37 kW at 690 V AC 50/60 Hz |
breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
[ICS] rated service short-circuit breaking capacity | 100% at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100% at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
control type | Rotary handle |
[In] rated current | 40A |
thermal protection adjustment range | 30…40 A |
magnetic tripping current | 560A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ith] conventional free air thermal current | 40 A conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
power dissipation per pole | 8W |
mechanical durability | 50000 cycles |
electrical durability | 50000 cycles for AC-3 at 415 V In |
maximum operating rate | 25 cyc/h |
rated duty | Continuous conforming to IEC 60947-4-1 |
tightening torque | 5 Nm on EverLink BTR screw connectors for cable 25 mm² 8 Nm on EverLink BTR screw connectors for cable 35 mm² |
mechanical robustness | Shocks: 15 Gn for 11 ms closed conforming to IEC 60068-2-27 Shocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27 Vibrations: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
height | 132mm |
width | 55mm |
depth | 136mm |
net weight | 0.96kg |
color | dark gray |
suitability for isolation | Yes conforming to IEC 60947-1 |