- Manufacturer: Pepperl+Fuchs
- Transmitter Power Supply KFD2-CRG2-1.D
- 1-channel signal conditioner
- 24 V DC supply (Power Rail)
- Input 2-wire and 3-wire transmitters and
2-wire current sources
- Output 0/4 mA ... 20 mA
- 2 relay contact outputs
- Programmable high/low alarm
- Linearization function (max 20 points)
- Line fault detection (LFD)
- Up to SIL 2 acc. to IEC 61508
General
specifications
- Signal type : Analog input
- Supply
- Connection : Power Rail or terminals 23+,
24-
- Rated voltage : 20 ... 30 V DC
- Rated current : approx. 130 mA
- Power dissipation : 2 W
- Power consumption : 2.5 W
- Input
- Connection : terminals 1, 2, 3
- Input I
- Input signal : 0/4 ... 20 mA
- Available voltage : = 15 V at 20 mA
- Open circuit voltage/short-circuit current
: 24 V / 33 mA
- Input resistance : 45 O (terminals 2, 3)
- Lead monitoring : breakage I < 0.2 mA;
short-circuit I > 22 mA acc. to NAMUR NE43
- Output
- Connection : output I: terminals 10, 11,
12
- output II: terminals 16, 17, 18
- Output: analog terminals 8+, 7-
- Output signal : 0 ... 20 mA or 4 ... 20 mA
- Output I, II : signal, relay
- Contact loading : 250 V AC / 2 A / cos f =
0.7 ; 40 V DC / 2 A
- Mechanical life : 5 x 107 switching cycles
- Energized/De-energized delay : approx. 20
ms / approx. 20 ms
- Output III : Signal, analog
- Current range : 0 ... 20 mA or 4 ... 20 mA
- Open loop voltage : max. 24 V DC
- Load : max. 650 O
- Fault signal : downscale I = 3.6 mA,
upscale I = 21.5 mA (acc. NAMUR NE43)
- Directive conformity
- Electromagnetic compatibility
- Directive 2004/108/EC : EN 61326-1:2006 ,
EN 61000-6-4:2007
- Low voltage
- Directive 2006/95/EC : EN 50178:1997
- Conformity
- Insulation coordination : IEC 62103
- Galvanic isolation : IEC 62103
- Electromagnetic compatibility : NE 21
- Degree of protection : IEC 60529
- Ambient conditions
- Ambient temperature : -20 ... 60 °C (-4
... 140 °F)
- Mechanical specifications
- Degree of protection : IP20
- Mass : 0.3 kg
- Dimensions : 4.0 x 11.9 x 11.5 cm (1.6 x
4.7 x 4.5 inch) , housing type C3
A brand-new, unused, unopened, undamaged item in its original packaging (where packaging is applicable). Packaging should be the same as what is found in a retail store,unless the item is handmade or was packaged by the manufacturer in non-retail packaging, such as an unprinted box or plastic bag
WE DO DIS MENTAL MOST USED MACHINE FOR RESELL
Item will be ship via economy shipping, delivery take about 2-5 working days to most countries or urgent shipment via FEDEX, UPS,OR DHL
+++Please read the Terms & Condition before purchase+++
ACCESSORIES
Any accessories, manuals, cable and etc that are not in the picture listing or mention, it is NOT INCLUDED.
INTERNATIONAL BUYER
Import duties, taxes, and charges are not included in the item price or shipping cost. These charges are the buyer's responsibility. Please check with your country's customs office to determine what these additional costs will be prior to bidding or buying
WARRANTY
Our warranty is valid for 14 days after initial receipt of item.
PAYMENT TERMS
PAYPAL, WIRE TRANSFER TT or Contact Us
RETURN POLICY
-For item condition not as described, defective. Please report to us for replacement or refund within 14 days of receipt.
-Returns must be in their original condition and include all shipped accessories. Shipping fees will NOT be credited for returns and ALL RETURN SHIPPING COSTS ARE THE RESPONSIBILITY OF BUYER.
- All items will ship with our warranty label. If any stickers have been removed or tampered, your refund will be canceled.