Technical specification
SENSING INPUT
Voltage 190-264V ac max, 1 phase 2 wire
Frequency 50-60HZ nominal
POWER INPUT
Voltage 140-220 V ac max, 3 phase,3 wire
CURRENT: 3A/phase
Frequency 100-120HZ nominal
OUTPUT
Voltage max 120V dc
Current continuous 2.7A dc
Intermittent 6A for 10 secs
Resistance 15 ohms minimum
REGULATION
+/-1%
THERMAL DRIFT
0.03% per deg.C change in AVR ambient
SOFT START PAMP TIME
3 sec
TYPICAL SYSTEM RESPONSE
AVR respone 10ms
Filed current to 90% 80ms
Machine Volts to 97% 300ms
EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 1k ohm 1 watt trimmer
UNDER FREQUENCY PROTECTION
Set point 95%HZ
Slope 170% down to 30HZ
UNIT POWER DISSIPATION
12 watts maximum
ANALOGUE INPUT
Maximum input +/-5V dc
Sensitivity 1V for 5% Generator Volts(adjustable)
Input resistance 1k ohm
QUADRATURE DROOP INPUT
10 ohms burden
Max.sensitivity:0.07A for 5% droop OPF
Max.input:0.33A
OVER EXCITATION PROTECTION:
Set point:75vdc
Time relay:10sec
Environmental
Vibration 20-100HZ 50mm/sec
100Hz 2kHz 3.3g
Operating temperature -40 to +70 C
Relative Humidity 0-70C 95%
Storage temperature -55 to +80 C
|