TeSys LRD,Deca thermal overload relays - 9...13 A - class 10A
LRD313

Main
rangeTeSys
TeSys Deca
product nameTeSys LRD
TeSys Deca
product or component typeDifferential thermal overload relay
device short nameLRD
relay applicationMotor protection
product compatibilityLC1D40A
LC1D50A
LC1D65A
network typeAC
DC
thermal overload classClass 10A conforming to IEC 60947-4-1
thermal protection adjustment range9…13 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
network frequency0...400 Hz
mounting supportPlate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
permissible current0.95 A at 380 V AC-15 for signalling circuit
0.06 A at 440 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
control typeRed push-button: stop
Blue push-button: reset
temperature compensation-20…60 °C