range | TeSys |
---|---|
product name | TeSys LRD |
product or component type | Non differential thermal overload relay |
device short name | LR3D |
relay application | Motor protection |
product compatibility | LC1D18 LC1D12 LC1D25 LC1D32 LC1D38 |
network type | DC AC |
thermal overload class | Class 20 conforming to IEC 60947-4-1 |
thermal protection adjustment range | 9…13 A |
[Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL Power circuit: 690 V conforming to IEC 60947-4-1 |
network frequency | 0...400 Hz |
---|---|
mounting support | Plate, with specific accessories Rail, with specific accessories Under contactor |
tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
auxiliary contact composition | 1 NO + 1 NC |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
permissible current | 3 A at 120 V AC-15 for signalling circuit 0.22 A at 125 V DC-13 for signalling circuit |
[Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
associated fuse rating | 4 A gG for signalling circuit 4 A BS for signalling circuit |
[Uimp] rated impulse withstand voltage | 6 kV |
phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
control type | Red push-button: stop Blue push-button: reset |
temperature compensation | -20…60 °C |