Direct online SIL starter TPRSS080 TeSys island, 80A AC-1, 66A AC-3, 37kW / 40hp

Main
rangeTeSys
product nameTeSys island
device short nameTPRSS
product or component typeSIL motor starter
motor starter typeDirect on line
device presentationDirect starter connected to an automation controller through a bus coupler
Operational only when connected to a bus coupler
function availableUpstream voltage presence detection
Electrical line and load protection
Power and energy monitoring when connected with TPRVM voltage module
Safe stop function available when connected with a TPRSM module
product compatibilityTPRBC bus coupler
TPRVM voltage interface module
TPRSM SIL interface module
poles description3P (3 NO)
utilisation categoryAC-1
AC-2
AC-3
AC-4
motor power kW18.5 kW at 230 V 50 Hz (AC-3)
37 kW at 380...415 V 50 Hz (AC-3)
37 kW at 440 V 50 Hz (AC-3)
37 kW at 500 V 50 Hz (AC-3)
37 kW at 690 V 50 Hz (AC-3)
motor power HP (UL / CSA)5 hp at 120 V AC 60 Hz for 1 phase motors
10 hp at 240 V AC 60 Hz for 1 phase motors
20 hp at 208 V AC 60 Hz for 3 phases motors
20 hp at 240 V AC 60 Hz for 3 phases motors
40 hp at 480 V AC 60 Hz for 3 phases motors
50 hp at 600 V AC 60 Hz for 3 phases motors
[Ue] rated operational voltage<= 690 V AC 47...63 Hz
[Ie] rated operational current66 A (at <50 °C) at <= 440 V AC-3
80 A (at <50 °C) at <= 440 V AC-1
[Ith] conventional free air thermal current80 A (at 50 °C)
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
overvoltage categoryIII
thermal protection adjustment range4…80 A
thermal overload classClass 5…30
resetRemotely or automatically
Irms rated making capacity1000 A at 440 V conforming to IEC 60947
rated breaking capacity1000 A at 440 V conforming to IEC 60947
[Icw] rated short-time withstand current900 A 40 °C - 1 s
520 A 40 °C - 10 s
260 A 40 °C - 1 min
110 A 40 °C - 10 min
average impedance1.5 mOhm - Ith 80 A 50 Hz
power dissipation per pole6.5 W AC-3
9.6 W AC-1
[Uc] control circuit voltage24 V DC supplied by the bus coupler
current consumption80 mA contactor sealed
500 mA contactor closing
power dissipation in W21.4 W at Ie AC-3