range | TeSys |
---|---|
product name | TeSys island |
device short name | TPRSS |
product or component type | SIL motor starter |
motor starter type | Direct on line |
device presentation | Direct starter connected to an automation controller through a bus coupler Operational only when connected to a bus coupler |
function available | Upstream voltage presence detection Electrical line and load protection Power and energy monitoring when connected with TPRVM voltage module Safe stop function available when connected with a TPRSM module |
product compatibility | TPRBC bus coupler TPRVM voltage interface module TPRSM SIL interface module |
poles description | 3P (3 NO) |
utilisation category | AC-1 AC-2 AC-3 AC-4 |
motor power kW | 18.5 kW at 230 V 50 Hz (AC-3) 37 kW at 380...415 V 50 Hz (AC-3) 37 kW at 440 V 50 Hz (AC-3) 37 kW at 500 V 50 Hz (AC-3) 37 kW at 690 V 50 Hz (AC-3) |
motor power HP (UL / CSA) | 5 hp at 120 V AC 60 Hz for 1 phase motors 10 hp at 240 V AC 60 Hz for 1 phase motors 20 hp at 208 V AC 60 Hz for 3 phases motors 20 hp at 240 V AC 60 Hz for 3 phases motors 40 hp at 480 V AC 60 Hz for 3 phases motors 50 hp at 600 V AC 60 Hz for 3 phases motors |
[Ue] rated operational voltage | <= 690 V AC 47...63 Hz |
[Ie] rated operational current | 66 A (at <50 °C) at <= 440 V AC-3 80 A (at <50 °C) at <= 440 V AC-1 |
[Ith] conventional free air thermal current | 80 A (at 50 °C) |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 |
overvoltage category | III |
thermal protection adjustment range | 4…80 A |
thermal overload class | Class 5…30 |
reset | Remotely or automatically |
Irms rated making capacity | 1000 A at 440 V conforming to IEC 60947 |
rated breaking capacity | 1000 A at 440 V conforming to IEC 60947 |
[Icw] rated short-time withstand current | 900 A 40 °C - 1 s 520 A 40 °C - 10 s 260 A 40 °C - 1 min 110 A 40 °C - 10 min |
average impedance | 1.5 mOhm - Ith 80 A 50 Hz |
power dissipation per pole | 6.5 W AC-3 9.6 W AC-1 |
[Uc] control circuit voltage | 24 V DC supplied by the bus coupler |
current consumption | 80 mA contactor sealed 500 mA contactor closing |
power dissipation in W | 21.4 W at Ie AC-3 |