Product data sheet Specifications Discontinued - Service only variable speed drive ATV312 - 5.5kW - 15kVA - 232W - 380..500 V3-phase supply ATV312HU55N4 Discontinued on: 26 January 2021 To be end-of-service on: 01 January 2026 Main Range of product Altivar 312 Product or component type Variable speed drive Product destination Asynchronous motors Product specific application Simple machine Assembly style With heat sink Component name ATV312 Motor power kW 5.5 kW Motor power hp 7.5 hp [Us] rated supply voltage 380...500 V - 15...10 % Supply frequency 50...60 Hz - 5...5 % Network number of phases 3 phases Line current 21.9 A at 380 V, Isc = 22 kA 16.5 A at 500 V EMC filter Integrated Apparent power 15 kVA Maximum transient current 21.5 A for 60 s Power dissipation in W 232 W at nominal load Speed range 1…50 Asynchronous motor control profile Factory set : constant torque Sensorless flux vector control with PWM type motor control signal Electrical connection Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6 terminal 2.5 mm² AWG 14 L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 16 mm² AWG 6 Supply Internal supply for logic inputs: 19...30 V 100 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (2.2 to 10 kOhm): 10...10.8 V 10 mA, protection type: overload and short-circuit protection Communication port protocol Modbus CANopen IP degree of protection IP20 on upper part without cover plate IP21 on connection terminals IP31 on upper part IP41 on upper part Option card Communication card for CANopen daisy chain Communication card for DeviceNet Communication card for Fipio Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Jul 11, 2022 1 Communication card for Modbus TCP Communication card for Profibus DP Complementary Supply voltage limits 323…550 V Prospective line Isc 22 kA Continuous output current 14.3 A at 4 kHz Output frequency 0…500 Hz Nominal switching frequency 4 kHz Switching frequency 2...16 kHz adjustable Transient overtorque 170…200 % of nominal motor torque Braking torque 150 % during 60 s with braking resistor 100 % with braking resistor continuously 150 % without braking resistor Regulation loop Frequency PI regulator Motor slip compensation Automatic whatever the load Adjustable Suppressable Output voltage <= power supply voltage Tightening torque Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6: 0.6 N.m L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 2.5 N.m Insulation Electrical between power and control Analogue input number 3 Analogue input type AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance: 30000 Ohm AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 Ohm AI3 configurable current 0...20 mA, impedance: 250 Ohm Sampling duration AI1, AI2, AI3: 8 ms analog LI1...LI6: 4 ms discrete Response time AOV, AOC 8 ms for analog R1A, R1B, R1C, R2A, R2B 8 ms for discrete Linearity error +/- 0.2 % for output Analogue output number 1 Analogue output type AOC configurable current: 0...20 mA, impedance: 800 Ohm, resolution: 8 bits AOV configurable voltage: 0...10 V, impedance: 470 Ohm, resolution: 8 bits Discrete input logic Logic input not wired (LI1...LI4), < 13 V (state 1) Negative logic (source) (LI1...LI6), > 19 V (state 0) Positive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1) Discrete output number 2 Discrete output type Configurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC - 100000 cycles Configurable relay logic: (R2A, R2B) NC - 100000 cycles Minimum switching current R1-R2 10 mA at 5 V DC Maximum switching current R1-R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms R1-R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms R1-R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms R1-R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 ms Discrete input number 6 Discrete input type (LI1...LI6) programmable at 24 V, 0…100 mA for PLC, impedance: 3500 Ohm Acceleration and deceleration ramps Linear adjustable separately from 0.1 to 999.9 s S, U or customized Braking to standstill By DC injection Protection type Input phase breaks: drive Line supply overvoltage and undervoltage safety circuits: drive Line supply phase loss safety function, for three phases supply: drive Motor phase breaks: drive Overcurrent between output phases and earth (on power up only): drive Overheating protection: drive Short-circuit between motor phases: drive 2 Jul 11, 2022 Thermal protection: motor Insulation resistance >= 500 mOhm 500 V DC for 1 minute Local signalling 1 LED (red) for drive voltage Four 7-segment display units for CANopen bus status Time constant 5 ms for reference change Frequency resolution Analog input: 0.1...100 Hz Display unit: 0.1 Hz Connector type 1 RJ45 for Modbus/CANopen Physical interface RS485 multidrop serial link Transmission frame RTU Transmission rate 10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen 4800, 9600 or 19200 bps for Modbus Number of addresses 1…127 for CANopen 1…247 for Modbus Number of drive 127 for CANopen 31 for Modbus Marking CE Operating position Vertical +/- 10 degree Outer dimension 442 x 239 x 192 mm 300 x 210 x 170 mm 232 x 180 x 170 mm 402 x 239 x 192 mm Height 232 mm Width 180 mm Depth 172 mm Net weight 6.5 kg Environment Dielectric strength 2410 V DC between earth and power terminals 3400 V AC between control and power terminals Electromagnetic compatibility 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Standards IEC 61800-5-1 IEC 61800-3 Product certifications GOST DNV NOM UL CSA C-Tick Pollution degree 2 Protective treatment TC Vibration resistance 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 Shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27 Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3 5…95 % without dripping water conforming to IEC 60068-2-3 Ambient air temperature for storage -25…70 °C Ambient air temperature for operation -10…50 °C without derating (with protective cover on top of the drive) -10…60 °C with derating factor (without protective cover on top of the drive) Operating altitude <= 1000 m without derating 1000...3000 m with current derating 1 % per 100 m Jul 11, 2022 3 Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 6.02 kg Package 1 Height 22.476 cm Package 1 width 26.31 cm Package 1 Length 29.892 cm Unit Type of Package 2 PAL Number of Units in Package 2 18 Package 2 Weight 115.2 kg Package 2 Height 77 cm Package 2 width 60 cm Package 2 Length 80 cm Unit Type of Package 3 S04 Number of Units in Package 3 2 Package 3 Weight 13.171 kg Package 3 Height 30 cm Package 3 width 40 cm Package 3 Length 60 cm