Module overview
For various applications, the developed general data acquisition module is widely used in various industries such as building, HVAC, fire protection, water supply, petrochemical, environmental protection, etc. It is used by most system integrators, automation companies and research institutes. High character ratio, stable and reliable data acquisition module. Special applications Customers who need cooperation, please contact us!
=> Support multiple types of PLC;
=> Support configuration software such as Kingview, Force Control, MCGS;
=> Support RS232, RS485 interface, Modbus protocol touch screen, text screen;
=> Support all standard Modbus devices online communication;
=> If you buy a large quantity, support custom function modules;
=> R&D personnel directly face customer technical support and assist customers to complete the project;
CPU: imported chip, 32-bit ATMEL ARM high-speed processor, 72MHZ
Operating system: GCOS, 10ms scheduling mechanism
Power supply voltage: 7-35VDC @2W, power reverse polarity protection, isolation design
Communication interface: DCDC isolation design, 2500V lightning protection, ESD, overvoltage, overcurrent protection
Dimensions: Volume (L x W x H): 155 x 95 x 39 (mm)
Installation method: screw fixing or rail installation
Environmental index: -40~85℃, 5%~95%RH non-condensing, IP20 protection
Hardware watchdog: 1.5 seconds hardware watchdog protection system
Channel isolation: 2500VDC isolation, anti-interference protection design. Since 1997, the product has been used stably in industrial sites
Communication interface: RJ45 interface
Communication protocol: standard MODBUS TCP protocol
Communication rate: communicate with the host computer, more than 1000 times/second
Communication bandwidth: 10M/100Mbps, real high-speed Ethernet
IP address: 192.168.1.75
Port number: 502
Support network cable: both crossover network cable and direct connection network cable are available, and the module can be self-adaptive
Number of channels: 1 RS485, 1 RS232
Baud rate: 1200~115200, default 9600
Parity check: odd check, even check, no check
Start bit: 1 bit
Data bits: 8 bits
Stop bits: 1, 2 bits
Communication protocol: MODBUS RTU
Default parameter: 9600.N.8.1, station number: 1
POWER light: Displays the power status
RUN light: module running indication, flashes once per second
485 lights: RS485 send data indication
232 lights: RS232 send data indication
IO lights: Each digital IO has a corresponding indicator light
Modbus address: 40059--40074
Function code: 03, address: 58
Factory default: current input: 4-20mA, 0-20mA [compatible]
Voltage input: 0-5V, 1-5V, 0-10V
Two steps to change the type:
1. Open "AI Configuration Software" and select the type;
2. Open the cover of the module, each channel has a jumper cap:
---Short 2 pins on one side of the 'chip': "voltage type"
---Short 2 pins on one side of the 'terminal': "current type"
Data accuracy: 0.1% accuracy, 12 bits
Refresh frequency: update all I/O point data once in 0.1 seconds
The corresponding value divided by 1000 is the actual signal size:
4~20mA: 4000~20000 <16-bit integer>
0~20mA: 0000~20000
0~5V: 0000~5000
0~10V: 0000~10000
Current and voltage calculation formula:
register reading / 1000
Example: read 40051 register data == 4000
Then the corresponding current = 4000 / 1000 = 4mA
​
Two-wire connection:
The meter is positively connected to the power supply;
The meter is negatively connected to AI;
The power supply is negatively connected to AI-COM;
Three-wire connection:
The instrument is connected to AI;
The meter is negatively connected to COM;
Four-wire connection:
The instrument is connected to AI;
The meter is negatively connected to COM;
Function 1: modify the corresponding value;
Factory default 4-20mA corresponding: 4000-20000<register>
Function 2: Modify the signal type:
0-5V, 1-5V, 0-10V, 0-20mA;
4-20mA minimum 0mA: AI=0 when disconnected, it is convenient for users to check whether the connection is bad;
4-20mA minimum 4mA: AI=4mA when the line is disconnected, that is, the AI reading is always greater than 4mA;
Modbus register: 40051--40058
Function code: 03, address 50
Temperature range: -200 to 320°C
Accuracy: 0.1°C
Input mode: two or three wire system
Data chip: imported industrial chip
Corresponding Modbus register data:
-2000 to 3200 <signed 16-bit integer>
Divided by 10 is the actual temperature value
​