Module overview

For various applications, the developed general data acquisition module is widely used in various industries such as building, HVAC, fire protection, water supply, petrochemical, environmental protection, etc. It is used by most system integrators, automation companies and research institutes. High character ratio, stable and reliable data acquisition module. Special applications Customers who need cooperation, please contact us!

=> Support multiple types of PLC;

=> Support configuration software such as Kingview, Force Control, MCGS;

=> Support RS232, RS485 interface, Modbus protocol touch screen, text screen;

=> Support all standard Modbus devices online communication;

=> If you buy a large quantity, support custom function modules;

=> R&D personnel directly face customer technical support and assist customers to complete the project;

CPU: imported chip, 32-bit ATMEL ARM high-speed processor, 72MHZ

Operating system: GCOS, 10ms scheduling mechanism

Power supply voltage: 7-35VDC @2W, power reverse polarity protection, isolation design

Communication interface: DCDC isolation design, 2500V lightning protection, ESD, overvoltage, overcurrent protection

Dimensions: Volume (L x W x H): 155 x 95 x 39 (mm)

Installation method: screw fixing or rail installation

Environmental index: -40~85℃, 5%~95%RH non-condensing, IP20 protection

Hardware watchdog: 1.5 seconds hardware watchdog protection system

Channel isolation: 2500VDC isolation, anti-interference protection design. Since 1997, the product has been used stably in industrial sites

Communication interface: RJ45 interface

Communication protocol: standard MODBUS TCP protocol

Communication rate: communicate with the host computer, more than 1000 times/second

Communication bandwidth: 10M/100Mbps, real high-speed Ethernet

IP address: 192.168.1.75

Port number: 502

Support network cable: both crossover network cable and direct connection network cable are available, and the module can be self-adaptive

Number of channels: 1 RS485, 1 RS232

Baud rate: 1200~115200, default 9600

Parity check: odd check, even check, no check

Start bit: 1 bit

Data bits: 8 bits

Stop bits: 1, 2 bits

Communication protocol: MODBUS RTU

Default parameter: 9600.N.8.1, station number: 1

POWER light: Displays the power status

RUN light: module running indication, flashes once per second

485 lights: RS485 send data indication

232 lights: RS232 send data indication

IO lights: Each digital IO has a corresponding indicator light

Modbus address: 40059--40074

Function code: 03, address: 58

Factory default: current input: 4-20mA, 0-20mA [compatible]

Voltage input: 0-5V, 1-5V, 0-10V

Two steps to change the type:

1. Open "AI Configuration Software" and select the type;

2. Open the cover of the module, each channel has a jumper cap:

---Short 2 pins on one side of the 'chip': "voltage type"

---Short 2 pins on one side of the 'terminal': "current type"

Data accuracy: 0.1% accuracy, 12 bits

Refresh frequency: update all I/O point data once in 0.1 seconds

The corresponding value divided by 1000 is the actual signal size:

4~20mA: 4000~20000 <16-bit integer>

0~20mA: 0000~20000

0~5V: 0000~5000

0~10V: 0000~10000

Current and voltage calculation formula:

register reading / 1000

Example: read 40051 register data == 4000

Then the corresponding current = 4000 / 1000 = 4mA

​

Two-wire connection:

The meter is positively connected to the power supply;

The meter is negatively connected to AI;

The power supply is negatively connected to AI-COM;

Three-wire connection:

The instrument is connected to AI;

The meter is negatively connected to COM;

Four-wire connection:

The instrument is connected to AI;

The meter is negatively connected to COM;

Function 1: modify the corresponding value;

Factory default 4-20mA corresponding: 4000-20000<register>

Function 2: Modify the signal type:

0-5V, 1-5V, 0-10V, 0-20mA;

4-20mA minimum 0mA: AI=0 when disconnected, it is convenient for users to check whether the connection is bad;

4-20mA minimum 4mA: AI=4mA when the line is disconnected, that is, the AI reading is always greater than 4mA;

Modbus register: 40051--40058

Function code: 03, address 50

Temperature range: -200 to 320°C

Accuracy: 0.1°C

Input mode: two or three wire system

Data chip: imported industrial chip

Corresponding Modbus register data:

-2000 to 3200 <signed 16-bit integer>

Divided by 10 is the actual temperature value

​

​