VEEDER-ROOT VERBIAGE - Preferred Wiring Type 

Use #14 - #18 AWG stranded copper, shielded cable (REQUIRED) and manufactured with a material suitable for the environment, such as Carol C2534, Belden 88760, or Belden 88760 Equivalent. Wiring to be installed as a Class 1 circuit with the following provisions: This equivalent cable is exactly the same wire without the high price.

• Wire run must not exceed 1000 feet to meet intrinsic safety requirements,

• Capacitance does not exceed 100 pf/ft,

• Inductance does not exceed 0.2 ìH/ft.

Alternate Wiring Type - When Approved by the Local Authority Having Jurisdiction!

 Use #22 AWG stranded copper, shielded cable (REQUIRED) and manufactured with a material suitable for the environment, such as Belden 88761 or Equivalent. Wiring to be installed as a Class 1 circuit with the following provisions:

• Wire run must not exceed 750 feet to meet intrinsic safety requirements,

• Capacitance does not exceed 100 pF/ft,

• Inductance does not exceed 0.2 ìH/ft.

Splices

Veeder-Root recommends that no splices be made in the wire run between the Probes/Sensors and the Tank Monitor.  Each splice degrades signal strength and could result in poor system performance.

 