Range of product | Modicon Quantum automation platform |
---|---|
Product or component type | Unity processor |
Clock frequency | 266 MHz |
---|---|
Number of slots | 16 6 2 10 4 |
Number of racks | 2 - local |
Number of distributed I/O station | 63 1 1 Modbus Plus |
Number of remote I/O station | 31 - 2 S908 remote I/O 31 - 2 ethernet Quantum remote I/O 31 - 2 ethernet X80 remote I/O |
Discrete I/O number | 8000 inputs, 8000 outputs - distributed - per network Modbus Plus Unlimited (26 slots max) - local Unlimited (31 drops of 28 slots max) - ethernet remote I/O 31744 inputs, 31744 outputs - S908 remote I/O |
Analogue I/O number | 500 inputs, 500 outputs - distributed - per network Modbus Plus Unlimited (26 slots max) - local Unlimited (31 drops of 28 slots max) - ethernet remote I/O 1984 inputs,1984 outputs - remote |
Application specific I/O | Counter Accurate time stamping Serial link High-speed interrupt inputs |
Communication service | Ethernet router |
Number of optional modules | 6 Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max) |
Maximum number of connections | 1 USB 2 AS-Interface - distributed 4 AS-Interface - remote 6 Ethernet TCP/IP - local 6 Modbus Plus - local 6 Profibus DP - local 1 Modbus RS232/485 Modbus/ASCII) |
Integrated connection type | 1 Modbus Plus 1 Ethernet TCP/IP 1 Modbus 1 USB |
Checks | Process control |
Memory description | Expandable 7168 kB - program with PCMCIA card Expandable 8 MB - file storage with PCMCIA card Internal RAM 3072 kB |
Switch function | Key switch memory port on/off |
Application structure | 1 cyclic/periodic master task - 1 periodic fast task - 128 I/O interrupt tasks - 128 interrupt tasks - 32 timer interrupt tasks - 4 auxiliary tasks - |
Number of instructions per ms | 10.28 Kinst/ms 100 % Boolean 10.07 Kinst/ms 65 % Boolean and 35 % numerical |
System overhead | 0.2 ms fast task 1 ms master task |
Bus current requirement | 2760 mA |
Local signalling | Ethernet activity (COM) 1 LED green) Ethernet collision 1 LED red) |
Electrical connection | 1 female connector SUB-D 9 for connecting to the Modbus Plus network 1 connector RJ45 for connecting Ethernet network 1 connector RJ45 for connecting Modbus bus |
Product certifications | CSA Misc (Marine) UL GOST CE |
---|---|
Standards | HazLoc |