Harland Protect UPS-M-PX 11kVA 10kW Marine Ship 1 Phase UPS Power  + Cabinet 240V
Model: Protect UPS-M-PX
P/N: 9PX11KiPM
P/N: SC240RT

New
Built for a showroom display - never been used
Not Supplied With Batteries
Included
  • 1 x Harland Protect UPS-M-PX 11kVA 10kW 3 Phase UPS/Battery Cabinet NO BATTERIES
  • 1 x Eaton 9PX 11kVA 10kW RackMount UPS - 9PX11KiPM
  • 1 x Eaton UPS Battery Supercharger Module - SC240RT
  • 1 x Battery Tray On Runners (for easy maintenance)
  • 1 x Integrated Maintenance Bypass Switch
  • 1 x Auto Input Changeover
  • 1 x Output Distribution
  • 2 x IP54 Air Filters

Protect UPS M-PX Cabinet
Specification
Output Rating @ 40°C: Max 11 kVA/10 kW
Output Rating @ 45°C: Max 6.1kVA/4.25kW
UPS Module: Eaton 9PX range on-line double conversion with integral static bypass
Battery Autonomy: 5 - 6 minutes (normally 30 minutes)
System IP Rating: IP20 - IP54 (normally IP54)
Enclosure: 2mm welded steel rugged construction with base mounted cable entry gland plate; Fitted with fixing assembly, lifting eyes and AVM's
Finish: Standard colour RAL7035 (other colours available upon request)
Dimension(H x W x D): 1700mm x 600mm x 850mm
Weight: 600kg 

Eaton 9PX 5-11kVA 10kW RackMount UPS - 9PX11KiPM
Specification
General
  • Topology: On-line double conversion with PFC (Power Factor Correction) system
  • Configuration: Rack/Tower
  • Part Number: 9PX11KiPM and 9PXEBM240
  • Rating (VA/Watts): 11000/10000
  • Dimensions (H x W x D, mm): 260 (6U) x 440 x 685
  • Weight (kg): 86
Electrical Input
Connection
  • Input Voltage Range: 176-276V without derating (up to 100–276V with derating)
  • Nominal Voltage: 200/208/220/230/240/250V
  • Frequency: 50/60 Hz autoselection
  • Frequency Range: 40-70 Hz
  • Short Circuit Current: 150 A
  • THDI: <5%
Electrical Output
  • Voltages: 200/208/220/230/240/250V +/– 1%
  • Voltage THD: < 2%
  • Overload Capacity: 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
  • Efficiency (Normal Mode): Up to 95% in Online mode, 98% in Hi-Efficiency mode
  • Output Frequency: 50/60 Hz autoselect, frequency converter as standard
  • Load Crest Factor: 3:1
Battery
  • Battery Management: ABM and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
  • Extended Battery Capability: EBM (3U)
Communications
  • User Interface: Multilingual graphical LCD display
  • Communication Ports: 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation.
  • Communication Slot: 1 slot for Network-MS card, ModBus-MS or Relay-MS cards

Environmental & Standards
  • Audible Noise: <50dB
  • Operating Temperature: 0 to 40°C continuous
  • Safety markings: IEC/EN 62040-1, UL 1778, CSA 22.2
  • EMC Markings: IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance), C-Tick
  • Approvals: CE, CB report (TUV), UL (Power Module)

Eaton UPS Battery Supercharger Module - SC240RT
Specification
Weight & dimensions
  • Width: 439.4  mm
  • Depth: 680.7  mm
  • Height: 129.5  mm
  • Weight: 15422  g
Certificates
  • Certification: CE, cULus, NOM  
Performance
  • Type: Indoor battery charger 


VAT @ 20% INCLUDED IN PRICE - VAT INVOICE PROVIDED
£2000 excluding VAT

VAT IS NOT PAYABLE BY PURCHASERS OUTSIDE OF THE UK
TH 229605