Ground resistance measurement range: 3 ranges 20Ω / 200Ω / 2000Ω
Industry's fastest response speed 2 seconds
Noise resistant! Can measure up to ground voltage 25V
Accurately even in an environment with large auxiliary ground resistance Measurable
Achieves continuous measurement of 10,000 times
A to D types can be measured by precision measurement (3-pole method). Supports simple measurement (2-pole method)
・ Industry's fastest response speed of 2 seconds
・ Noise resistant! Can measure up to 25V ground voltage
・ Accurate even in an environment with large auxiliary ground resistance Measurable
・ Achieves 10,000 continuous measurements
・ Measurement of A to D types is possible by precision measurement (3-pole method). Also supports simple measurement (2-pole method)
◆ Specifications
Ground resistance range: 20Ω
[Measurement range] 0.00 to 20.00Ω
[Accuracy * 1] ± 1.5% rdg ± 0.08 Ω * 2
[Allowable range of auxiliary ground resistance * 3] Within 10 kΩ
[Comparator threshold] 10 Ω
Ground resistance range: 200 Ω
[Measurement range] 0.0 ~ 200.0Ω
[Accuracy * 1] ± 1.5% rdg ± 4dgt
[Auxiliary ground resistance tolerance * 3] Within 50kΩ
[Comparator threshold] 100Ω
Resistance range: 2000Ω
[Measurement range] 0 to 2000Ω
[Accuracy * 1] ± 1.5% rdg ± 4dgt
[Auxiliary ground resistance tolerance * 3] Within 100kΩ
[Comparator threshold] 500Ω
[Measurement range of voltmeter] AC0.0 ~ 300.0V [45 ~ 65Hz] DC ± 0.0 ~ ± 300.0V
[Accuracy] ± 1% rdg ± 4dgt
/> [Compliant Standards] IEC 61010-1 CAT IV 100 V / CAT III 150 V / CAT II 300 V Contamination degree 3, IEC 61010-2-030, IEC 61010-031, IEC 61557-1, -5, IEC 60529 IP67, IEC 61326-1, -2-2 (EMC), EN50581 (RoHS)