Lot Of 50 New EYE LIGHTING 50EYE124BGJJF
Outdoor Locking Photoelectric Photo Light Sensors
SHIPS TO ADDRESSES WITHIN THE LOWER 48 STATES ONLY PLEASE
Applications Include
LED, HID, Induction, Fluorescent or Halogen Systems; Roadways;
High Surge Areas; Street Lighting; Parking Lots; Security Lighting
Rated 105-305VAC for 120, 208, 240 and 277VAC systems
Will operate down to 90VAC
Control rated -40° to +70°C. Base rated for 105°C interface
temperature per C136.10
FR4 fiberglass printed circuit board
Silicon light sensor
2-5 second Turn OFF delay
ANSI Standard 1.5±0.5 fc Turn ON, Turn OFF is 1.5 times the Turn ON level
Surge protection: Dual 25mm 420 joules. All controls are rated for multiple
surges at one minute intervals
>0.070 inch (1.78 mm) cover thickness
Solid brass legs
Load rating: 1800VA HID ballast or 1000W (10A) electronic LED driver
Fail OFF design series
» Use Fail OFF controls in situations where fixture life may be
compromised by being ON during the day in unlikely event
of a photocontrol failure
Upgrade from standard control with dual 420 MOV’s
Sealed relay
Cover Color - black
50-piece carton quantity
120-277VAC, two 25 mm MOVs each rated 420 joules for multiple surges. Black cover. Fail OFF.
Sample Specification
for Silicon Multivolt RoHS Compliant Photocontrols – BG Series
1.
Photocontrol: Shall be a Locking Type (aka twist lock).
2.
Line voltage: 105-305VAC @ 50/60 hertz.
3.
Load rating: Shall be at least 1800VA. Control must be
able to operate incandescent, ballast, LED and lighting
contractor type loads.
4. Control relay: Shall be sealed.
5. Turn ON: Shall be 1.5±0.5 fc. Turn OFF shall be 1.5 times
the turn ON level.
6. Photosensor: Sealed silicon sensor. Cadmium sulphide
cells are not acceptable.
7. Failure mode: Control will fail OFF per ANSI definition.
Relay must use normally open contacts.
8. Time delay: Control must have instant ON and
2-5 seconds “OFF” delay.
9. Surge protection: Each MOV shall be rated a minimum of
420 joules and 9500 amp surge.
10. Housing: Shall be black, opaque and of an impact and
UV resistant material. Impact resistance of housing shall
be greater than 1.0 ft-lbs at -20°C. Top of cover 0.070 inch
(1.78 mm) or thicker.
11. Drop test: Control must be capable of withstanding a
drop of 3 feet (1 m) to a concrete floor without causing
damage to the housing or changing electrical operation.
12. Markings: The following must appear on the control:
month/year of manufacture, model description, operating
voltage range and load rating.
13. Power consumption: Shall consume 0.5 watts or less
at 120VAC.
14. Environmental: Shall be RoHS compliant. It shall not
contain lead, cadmium, mercury or hexavalent chromium.
Pigments in plastic parts shall not contain bromine
compounds or heavy metal pigments.