Sentinel Dual SDU

SDU 10000

INPUT

 

Dual Input

no

Rated power

10000 VA

Voltage

220 / 230 / 240 V

Voltage tolerance

230 V ±20%

Frequency

50 / 60 Hz ±5

Power factor

>0.98

Current distorsion

≤2%

BY PASS

 

Voltage tolerance

180 / 264 V (selectable in ECO Mode or SMART ACTIVE Mode)

Frequency tolerance

Selected frequency ±5% (selectable by user)

OUTPUT and INVERTER OUTPUT

 

Rated power

10000 VA

Active power

10000 W

Crest factor (Ipeak/Irms)

3 : 1

Waveform

Sinusoidal

Frequency

50 / 60 Hz selectable

Voltage distortion with non-linear load

<3%

Voltage distortion with linear load

<1%

BATTERIES

 

Type

VRLA AGM maintenance-free lead based

Typical recharge time

4-6 h

ENVIRONMENTAL

 

Color

Black RAL 9005

Communication

USB / RS232 / slot for communications interface / REPO + Input contact

Accessories provided

USB cable; handles kit

Protections

Overcurrent - short circuit - overvoltage - undervoltage - temperature - excessive low battery

Noise (at 1 m)

<48 [bBA] (ECO Mode)

Operating temperature

0 °C - +40 °C

Relative humidity

5-95% non-condensing

Output sockets

Terminal block + 2 IEC 320 C13 + 3 IEC 320 C19

Standards

European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111

DATA

 

Weight

20+62 kg

Dimensions (h w d)

2x (448x131x640) Tower - 2x (3Ux19”x640) Rack mm

Input phases

1

Output phases

1