TEC3622-14-000 | TSTAT, MSTP OR N2, FCU/VAV, 0-10VDC PROP, DEHUMID, FULL COLOR, WHITE, JCI LOGO | JOHNSON CONTROLS



Supply Voltage

24 VAC

Type

Communicating

Display

Touchscreen

Controls Outputs

On/Off or Floating fan coil and zoning

PRODUCT SERIES SPECIFICATIONS

    Power Requirements:
  • 19 - 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safety extra-low voltage (SELV)
    Analog Output Rating (Prop. Control Models:
  • 0 - 10 VDC into 2k ohm resistance (min.)
    Relay Contact Rating (On/Off, Floating or Staged:
  • 19 - 30 VAC, 1.0 A max, 15 mA min., 3.0 A in-rush, Class 2 or SELV
    Economizer Control Models):
    Fan Relay Output Rating (On/Off, Floating, and:
  • 19 - 30 VAC, 1.0 A max, 15 mA min., 3.0 A in-rush
    Proportional Control Models):
    Auxillary Output Rating/Triac Outpus (On/Off, :
  • 19 - 30 VAC, 1.0 A max, 15 mA min., 3.0 A in-rush
    Floating, and Proportional Control Models):
    Binary Inputs:
  • Dry contact across terminal COM to terminals BI1, BI2, to COS
    Analog Inputs:
  • Nickel, platinum, A99B, 2.25k ohm negative temp. coefficient (NTC), 10k ohm NTC, 10k ohm NTC Type 3 across terminal
    :
  • COM to terminals R SEN or COS
    Temperature Sensor Type:
  • Local 1k ohm platinum sensor
    Connectors:
  • 18 AWG (1.0 mm dia) max, 22 AWG (0.6 mm dia) recommended
    MS/TP Network Guidelines:
  • Up to 100 devices max per Network Automation Engine (NAE); 4,000 ft. (1,219 m) max cable length (repeaters
    :
  • can be added to extend this length)
    Temperature Range:
    :
  • Backlit Display -40°F/-40°C to122.0 °F/50.0 °C in 0.5° increments
    :
  • Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
    :
  • Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
    Accuracy:
    :
  • Temperature +/- 0.9°F / +/-0.5°C at 70.0°F/21.0°C typical calibrated
    :
  • Humidity +/- 5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
    Minimimum Deadband:
  • 2F°/1C° between heating and cooling
    Occupancy Sensor Motion Detection:
  • Min. of 94 angular degrees up to distance of 15 ft. (4.6 m) based on a clear line of sight
    Ambient Conditions:
    :
  • Operating 32 to 122°F (0 to 55°C); 95% RH maximum, noncondensing
    :
  • Storage -22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
    Weight:
    :
  • Models without Occupancy Sensor .75 lbs (0.34 kg)
    :
  • Models with Occupancy Sensor .77 lbs (0.35 kg)
    Approvals:
  • CE, UL Listed, FCC Part 15.247 reg. for low power unlisted transmitters
    Warranty:
  • Two Configurable Binary Inputs
  • Field-Selectable BACnet MS/TP or N2 Networked (limited to TEC36XX-0X-000 models)
  • USB Port Configuration
  • Backlit Liquid Crystal Display (LCD)
  • Configurable Touchscreen UI
  • End of Line Switch
  • Onboard Occupancy Sensors (limited to TEC3XX1-0X-000 and TEC3XX3-0X-000 models)
  • On/Off, Floating, Proportional 0 to 10 VDC, and Single- or Two-Stage Control
  • Integral Humidity Sensor (limited to TEC3XX2-0X-000 and TEC3XX3-0X-000 models)
  • Multiple Fan Configurations for Fan Coil Equipment Types
  • Full Line of Remote TE-6300 Series Temperature Sensors
  • Built-in Schedule Object
  • Optimal Start
  • Auto-Tuned Control Loops
  • Load Shed

Details for TEC3622-14-000

TSTAT, MSTP OR N2, FCU/VAV, 0-10VDC PROP, DEHUMID, FULL COLOR, WHITE, JCI LOGO

The TEC3000 Series Thermostat Controllers are wireless, stand-alone, and field-selectable BACnet® Master-Slave/Token-Passing (MS/TP) or N2 networked devices that provide on/off, floating, and proportional control

Specifications

Item NumberTEC3622-14-000
BrandJohnson Controls
Thermostat TypeLow Voltage Thermostats

The TEC3000 Color Series Thermostat Controllers are wireless, stand-alone, and field-selectable BACnet® MS/TP or N2 networked devices that provide on/off, floating, and proportional control of the following: Local hydronic reheat valves Pressure-dependent VAV equipment with or without local reheat Two- or four-pipe fan coils Cabinet unit heaters Other zoning equipment using an on/off, floating, or 0 to 10 VDC proportional control input Single- or two-stage control of unitary rooftop units (RTUs) Single- or two-stage control of RTUs with economizers Single- or two-stage control of heat pumps Single- or two-stage control of heat pumps with economizers You can remote monitor and program the wireless and field-selectable BACnet MS/TP or N2 networked thermostat controllers through the building automation system, for efficient space temperature control. The wireless thermostat controllers feature a connection to the ZFR Pro wireless network. All models include a USB port configuration that reduces installation time by allowing simple backup and restore features from a USB drive, which enables rapid cloning of configuration between like units. The programming memory of all TEC3000 Series Thermostat Controllers is non-volatile. Some models feature a built-in occupancy sensing capability. These thermostat controllers use additional standby setpoints to maximize up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied times. A bright, high-definition capacitive touchscreen display provides responsive feedback and improved readability of text and icons. The home screen is configurable to Modern and Classic, and Light and Dark themes. The following fan configurations are supported for fan coil equipment types: Single-speed Multi-speed (two or three discrete speeds) Variable-speed/EC motors (0 to 10 VDC control)