Eaton 9PX 9PX5KP1 5kVA/4.5kW 208V w/120V Out PowerPass Distribution Module  UPS 

General
TopologyDouble-conversion online
ConfigurationRack/Tower
Catalog Number9PX5KP1
ColorBlack and silver
Rating (VA/Watts)5000/4500
 
DiagnosticsFull system self test at power up
UPS BypassMBP6K208 optional. Rear-mount 3U, 208V maintenance bypass for 5 and 6 kVA 9PX UPS models. Hardwired input. Hardwired and (2) L6-30R output.
Dimensions (H x W x D, inches)10.2 (6U) x 17.3 x 28.4
Dimensions (H x W x D, mm)259 (6U) x 439 x 721
Weight (kg)92
Weight (lbs)203
Warranty2 years
Rail Kit Included4-post rail kit and tower pedastals included
Remote Emergency Power off (REPO)ROO/RPO: Rear deck emergency stop connectors (for remote on/off and power off)
Contents
(Ships with the following items)
9PX5K 5kVA UPS
9PXPPDM1 PowerPass Distribution Module
Gigabit Network card (Network-M2)
4-post rail kit
User manual
Quick start guide
Tower pedestals
Intelligent Power Software Suite CD
RS-232 serial cable
USB cable
Cable gland for hardwire connection
Phillips head screw driver
Efficiency93% with resistive load
 
Electrical Input
Connection
(1) NEMA L6-30P

Input Cord6 feet (1.8 meters)
Input Voltage RangeFull load: 176-276V, Derating: 100-276V
Nominal Voltage208V default (200/208/220/230/240V)
Frequency50/60 Hz
Frequency Range60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
Input Power Factor>99
Input Current Distortion<5%
 
Electrical Output
Nominal Voltage120/240V default (200/208/220/230/240V)
Output voltage regulation±1% steady-state
Voltage THD<2% for linear loads
Output Receptacles
(6) NEMA 5-20R

(1) NEMA L6-30R

(1) NEMA L14-30R

Power Factor0.9
Transfer Time0 ms
Circuit Breaker(1) 30A for L6-30R; (1) 30A for L14-30R; (2) 20A for 5-20R


Optional Extended Battery Module9PXEBM180RT
Battery DescriptionSealed, lead-acid; maintenance free
Maximum number of extended battery modules (EBM)Add up to 4 extended battery modules (EBM)
Battery ManagementABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement
Battery ReplacementHot-swappable internal batteries and extended battery modules (EBMs)
Start On BatteryCold-start enabled; first cold start is always forbidden
 
Communications
User InterfaceGraphical display. UPS status in a single view.
LEDs4 status-indicating LEDs
Communication PortsRS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included
Communications Card SlotsGigabit Network Card (Network-M2) included
Power Management SoftwareEaton Intelligent Power Software Suite CD (included)
 
Environmental & Standards
RoHS ComplianceYes
Surge ProtectionIEEE ANSI C62.41 Cat B2
Audible Noise<45 dB at 1 meter
Operating Temperature0 to 40°C (32°F to 104°F)
Safety markingsCE / cULus / NOM
EMC MarkingsIEC 62040-2:2006 Cat C2 / CISPR22 Class A / FCC part 15 Class A
Storage Temperature0 to 35°C (32°F to 95°F); without batteries: -15 to 60°C (5°F to 140°F)
Relative Humidity0 to 95%
Altitude<1,000 meters for nominal power; 10% power derating every 1000 meters (up to 3000 meters)