TECHNICAL DATA FOR PVUC 24/24-10
Input rated voltage
24 Vdc
Input voltage range
20 - 30 Vdc
Current input (idle/charging/max.)
60 mA / 1 A / 11 A
Switching threshold for buffer mode
20 - 24 Vdc
Output rated voltage
24 Vdc
Output voltage normal operation
typ. Uin - 0.5 Vdc (10 A)
Output rated voltage, battery mode
20 - 24 Vdc (adjustable)
Resistance to reverse feed max.
35 Vdc
Output rated current
10 A
Buffer period
0.4 s (10 A) / 6.3 s (1 A)
Charging time
typ. 5 minutes
Internal fuse
No
Overload behaviour
Constant current (typ. 11 A)
Parallel connection
Yes
Serial operation
No
max. Power loss idling/nominal load
1.5 / 6.5 W
Efficiency
typ. 97 %
Type of the storage medium
Capacitors, internal
Operating status
LED green, LED red, LED yellow
Potential-free signal contact
Changeover contact
Active signal outputs
No
Display, interface
No
Approvals
cULus
Environment
Ambient temperature
14 °F to +140 °F
Storage temperature
-13 °F to +185 °F
Protection index
IP 20
Safety class
III, without PE connection
Reverse connection protection
Yes
Terminals input, (spring clamp terminal, pluggable)
max. 2.5 mm²
Terminals output, (spring clamp terminal, pluggable)
max. 2.5 mm²
Terminals signalling, (spring clamp terminal, pluggable)
max. 2.5 mm²
Mounting position
vertical
Fixing method
DIN rail system TS35
Width
2.24 inch
Height
5.00 inch
Depth
7.07 inch
Weight
2.20 lbs
General Data
Output rated voltage 24 Vdc
Protection index IP 20
Ambient temperature 14 °F / -10 °C to +140 °F / +60 °C
Output rated current 10 - 20 A
Efficiency typ. 97 %
Input rated voltage 24 Vdc
Service-friendly spring-loaded connector system
Panel installation on mounting rails
Electronic overcurrent and short-circuit protection
Reverse polarity protection
Configurable switch-in threshold
3 LEDs for signaling purposes
Isolated signal contact
Decoupled output
Parallel connection option