PACK CONTENTS

The pack contains the fixings necessary for a single leaf wall up to 2.4m / 8’

Packed in boxes of 10.

INSTALLATION GUIDE

Installation Note
Prior to installation remove any render or debris from the existing wall.

Internal Walls
1. Plumb the lower connector against the existing wall so that it will be central to the new wall.
2. Mark the position of the fixing holes. Each connector should be fixed at three points, the first and last slot and in the centre. Ensuring that one fixing is at the point where the two connectors slot together and overlap. Fixings should be into brickwork and not mortar joints.
3. Drill and plug using an 8mm masonry drill bit and the plugs provided.
4. Fix the bottom two holes lightly using the stainless steel coach screws and washers.
5. Slot the upper connector into the lower one and repeat the above stages. The upper connector can be cut to length if required.
6. Tighten all fixings using a 10mm socket or box spanner.
7. Build wall in the conventional way with a full mortar joint between the existing and the new wall. Ties should be inserted at a maximum of 300 centres, every third brick course or each block course. Ensure that the ties and connectors are completely embedded with mortar.

Cavity Walls
Each leaf requires a separate starter system.

External Walls
Ensure that the bottom edge of the connector is above the damp-proof course. A weather seal of approximately 10mm should be created between the connector and the existing wall using a flexible mastic sealant or a compressible sealing strip. Consult your Local Authority, as additional weatherproofing may be required in accordance with local building regulations.

The multi-purpose no flange profile that has been designed to cater for brick and block walls of widths from 60 to 250mm. Ideal for internal and external applications where both sides of the new wall are to be fair faced.

Installation - Use all specified fasteners. - Fasteners must be spaced evenly, unless otherwise specified, andinstalled into the bricks or block and not into mortar joints. - Insert wall ties provided at maximum 300mm centres, bedding the ties into the mortar joints. - Detailed site work instructions are provided with each wall connector system. - In exposed locations it may be necessary to incorporate additional protection, for example the insertion of a vertical dpc.