Key Benefits of the Vertiv™ Liebert® GXT5 UPS:
Liebert GXT5-2000LVRT2UXLN UPS Specifications
Mechanical | |
Height | 3.4" (85 mm.) |
Width | 16.9" (430 mm.) |
Depth | 18.5" (470 mm.) |
Weight | 47.4 lb (21 kg) |
Rack Height | 2U |
Color | Black |
Input AC | |
Range | Typical 120V Range: 60-150V |
Frequency | 40-70Hz; Auto Sensing |
Input Power Cord | NEMA L5-20P or 5-20P plug (5-20P adapter included) |
Output AC | |
Output Receptacles | L5-20R + 5-20R (x6) |
Voltage | Typical 120V 110/115/120VAC (user-configurable); ±3% |
Waveform | Sine wave |
Utility (AC) Mode Overload | >200% for 250ms; 150- 200% for 2 seconds 125- 150% for 50 seconds; 105-125% for 60 seconds |
Battery | |
Type | Valve-regulated, non-spillable, lead acid |
Backup Time | 4 Minutes (100% Load) 12.3 Minutes(50% Load) |
+1 External Battery Cabinet | 22 Minutes (100% Load) 53.6 Minutes(50% Load) |
Environmental | |
Operating Temperature | 32 to 104°F (0 to 40°C) |
Storage Temperature | -4 to 140°F (-20 to 60°C) |
Relative Humidity | 0% to 95%, non-condensing |
Operating Elevation | 10,000 ft. (3,000m) |
Storage Elevation | 50,000 ft. (15,000m) |
Audible Noise | < 46dBA max @ 3 ft. (1m) front and sides < 43dBA, at 3 ft. (1m) rear |
Agency | |
Surge Immunity | ANSI C62.41 Category B |
Transportation | ISTA Procedure 1A |
Safety | UL 1778 4th Edition and CSA 22.2 No. 107.1 |
Emissions | FCC Part 15 (Class A) - CISPR22 Class A (RFI) |
Warranty |
3 year warranty (Opt. 2 year) |