Brand new


The Flatpack2 HE SOLAR charger is

suitable for any telecom site with

autonomous (solar only) or hybrid solar

power. It can be used in parallel with any

other Flatpack2 rectifiers feed by

generator or unreliable mains on a hybrid

side.

The Flatpack2 HE SOLAR charger is fully

integrated with the standard Flatpack2

family which means it can be used in any

48V FP2 system solutions with “4AC”

power shelves and Smartpack controller.

Typically each charger is fed by one string

of 4 to 6 solar panels. Galvanic isolation

between solar panels and

batteries/telecom equipment provides

high level of surge protection and

reliability.


SOLAR CHARGER MODULE

INPUT DATA

Voltage Nominal: 170 – 230 VDC

Tolerances: 85-265 VDC

Start-up voltage 150VDC

Maximum Current 9.5 Arms maximum at nominal input and full load

10 Arms maximum at 85VDC and full load

Input Protection o Varistors for transient protection

o Fuse in both lines

o Reverse polarity

OUTPUT DATA

Voltage o Default: 53,5 VDC o Float/Boost: 48 – 57,6 VDC

For input voltages > 230VDC output

stand by/test voltage is limited

Maximum Output Power o 1500 W, derating below 170V input o 800W at 85V input

Maximum Current 31,3 Amps at 48 VDC

Current Sharing Passive, to optimize the power available from each string of solar panels

Static voltage regulation* ±0.5% from 10% to 100% load

Dynamic voltage regulation* ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms

Ripple and Noise* o < 250 mV peak to peak,

o 30 MHz bandwidth

o < 2 mV rms psophometric

Output Protection o Overvoltage shutdown

o Hot plug-in - Inrush current limiting

o Short circuit proof

o High temperature protection

o Fuse

* Based on power supplied not limited by solar panels

OTHER SPECIFICATIONS

Efficiency >96% at 30-80% load and 200VDC input

Isolation 3.0 KVAC – input and output

1.5 KVAC – input earth

0.5 KVDC – output earth

Alarms o High temperature shutdown

o Charger Failure

o Overvoltage shutdown on output

o Fan failure

o Low voltage alarm at 43.5V

o CAN bus failure

Warnings o Low input voltage

o Low temperature shutdown

o Charger in power derate mode

o Remote battery current limit

activated

o Input voltage out of range, flashing at

overvoltage

o Loss of CAN communication with

control unit, stand alone mode

Visual indications o Green LED: ON, no faults

o Red LED: charger failure

o Yellow LED : charger warning

Operating temp. -40 to +75°C (-40 to +167°F), derating linear above +55°C (+131°F) to 1200W at +75°C (+167°F)

Storage temp. -40 to +85°C (-40 to +185°F)

Cooling Fan (front to back airflow)

Fan Speed Temperature and current regulated

MTBF > 350,000 hours Telcordia SR-332 Issue I, method III (a) (Tambient : 25°C)

Acoustic Noise < 20dBA at nominal input and full load (Tambient <= 25°C)

< 56dBA at nominal input and full load (Tambient > 40°C)

Humidity Operating:

5% to 95% RH non-condensing

Storage:

0% to 99% RH non-condensing

Dimensions 109 x 41.5 x 327mm (W x H x D) (4.25 x 1.69 x 13”)

Weight 1.950 kg (4.3lbs)

APPLICABLE STANDARDS

Electrical safety IEC 60950-1

UL 60950-1

CSA 22.2

EMC ETSI EN 300 386 V.1.3.2

EN 61000-6-1 (immunity, light industry)

EN 61000-6-2 (immunity, industry)

EN 61000-6-3 (emission, light industry)

EN 61000-6-4 (emission, industry)

Environment ETSI EN 300 019-2-1 Class 1.2

ETSI EN 300 019-2-2 Class 2.3

ETSI EN 300 019-2-3 Class 3.2

ETSI EN 300 132-2

RoHS compliant

ORDERING INFORMATION

Part No. Description

241115.650 Flatpack2 48/1500 HE SOLAR